GE 8 Series Operating Manual page 66

Table of Contents

Advertisement

192 cells
Battery with expected trickle life 5 years
UPS model
10Ah
17Ah
SitePro 10 kVA
9
16
SitePro 15 kVA
-
11
SitePro 20 kVA
-
6
SitePro 30 kVA
-
SitePro 40 kVA
-
Stop Operation time
Residual battery autonomy time before UPS forced shutdown.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes (see tables).
Capacity
Ah capacity of the battery.
Cells
Number of cells of the battery.
Lead-Acid (VRLA):
NiCd:
Boost:
Example:
180 battery cells
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the battery manufacturer.
Configuration
CONFIGURATION
Save and exit ?
Yes
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Autonomy times for lead acid batteries (VRLA)
Autonomy at full load at PF=0.8
24/26
33Ah
38Ah
Ah
30/31
45
52
15/16
26
32
10/11
18
22
-
5/6
11
12
-
-
6
7
÷
177
192 cells
281 cells
÷
182
195 cells
30 blocks / 12 Vdc battery
CONFIGURATION screen
Screen to save the configuration of set parameters.
Any additional modification of setup parameters can be done
only from a GE SERVICE PERSON as it requires an access code.
U floating = 436 Vdc (2.27 Vdc - cell)
Battery with expected trickle life 10 years
2x38
65Ah
75Ah 100Ah 150Ah 200Ah 300Ah 400Ah 500Ah
Ah
105
-
135
-
62
-
84
117
42
-
58
84
27
-
36
50
18
-
24
6
60 blocks / 6 Vdc battery
-
-
-
-
-
-
-
-
135
-
-
-
84
117
-
-
58
84
135
-
180 blocks / 2 Vdc battery
Continue
Operating Manual SitePro 10-15-20-30-40 kVA / S8
-
-
-
-
-
Page 66/99