8.2.7 Restore to normal operation after "Load Off"

NOTE !
Make sure the UPS Parallel System to be status of the activation of "Load Off":
Switches Q1 and Q4 are closed (Pos. I),
Switches Q2 are open (Pos. O);
Battery fuse F8 – F9 are inserted;
LED Alarm is lit (load is not protected by UPS Parallel System);
LEDs Operation are Off.
View of the synoptic diagram, on all UPS units,
after pressing the key "Load Off".
1.
Reset "Load Off" of the Parallel System.
Restore the command "Load Off", on
anyone of the parallel units, by entering the
screen:
COMMANDS / RESET LOAD OFF
The load is powered by SitePro Parallel System
supplying the parallel bus.
LEDs Alarms are Off and the LEDs Operation
must be lit.
The synoptic diagram, on all UPS units, must
display
the
status
INVERTER".
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
"LOAD
SUPPLIED
BY
Home\ Commands
COMMANDS
RESET LOAD OFF
REQUEST LOAD OFF
Operating Manual SitePro 10-15-20-30-40 kVA / S8
Page 84/99