GE 8 Series Operating Manual page 53

Table of Contents

Advertisement

Code
Message
4562
DETOUR ON
4564
DETOUR OFF
4567
COMMAND LOAD ON MAINS
4568
COMMAND LOAD ON INVERTER
4572
NO MORE OVERLOAD
INVERTER AND MAINS
4580
SYNCHRONIZED
COMMAND NOT
4582
TO SYNCHRONIZE
4583
COMMAND TO SYNCHRONIZE
4600
COMMAND UPS ON
4601
COMMAND UPS STANDBY
4602
Q1 OPEN
4603
Q1 CLOSED
4699
BATTERY TEST IMPOSSIBLE
4763
REMOTE CONTROL ON
4764
REMOTE CONTROL OFF
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
The auxiliary contact indicates that manual bypass Q2 was
closed.
The auxiliary contact indicates that manual bypass Q2 was
opened.
The control unit received a command to transfer the load on
mains.
The control unit received a command to transfer the load on
inverter.
End of the overload condition detected with alarm 4570.
The
voltages
of
Inverter
synchronised.
Command not to synchronise with mains has been done for
mains BP out of tolerance (4410) or setting parameters.
Command to synchronise with mains has been done for
mains BP OK (4411) or setting parameters.
The SEM mode function has been disabled or the
programmed time is expired.
The UPS returns to VFI mode supplying the load normally by
inverter.
The function SEM mode is enabled, and according to the
time program the UPS will run in SEM mode, supplying the
load normally by mains.
The auxiliary contact indicates that the output switch Q1
was opened.
The auxiliary contact indicates that the output switch Q1
was closed.
Not possible to start battery test (is postponed):
No mains rectifier or bypass.
-
Battery not fully charged.
-
Load is below 10% or above 80%.
-
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (service only):
0 = Only local panel.
1 = Only serial port on CI.
2 = Both.
.
Inverter cannot be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (service only):
0 = Only local panel.
1 = Only serial port on CI.
2 = Both.
Meaning
and
mains
bypass
Operating Manual SitePro 10-15-20-30-40 kVA / S8
are
Page 53/99