Messages List - GE 8 Series Operating Manual

Table of Contents

Advertisement

7.3.3 Messages list

Code
Message
4002
WATCHDOG RESET
4111
RECTIFIER MAINS OK
4119
BATTERY TEST STARTED
4120
BATTERY TEST STOPPED
4161
RECTIFIER ON
4162
RECTIFIER OFF
4163
GENERATOR ON
4164
GENERATOR OFF
INVERTER CANNOT BE
4302
TURNED ON
INVERTER CANNOT BE
4303
TURNED OFF
4361
INVERTER ON
4362
INVERTER OFF
4411
BYPASS MAINS OK
4500
COMMAND LOAD OFF
4521
NO BYPASS POWER
4534
MULTIPLE LOAD TRANSFER
4535
BYPASS LOCKED
4536
BYPASS FREE
4561
LOAD OFF
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
The microprocessor has detected an incorrect operation:
transfers the load on mains and performs a program reset.
The inverter will restart automatically and will supply the
load.
Rectifier input mains is again within the admitted tolerance
(voltage, frequency and phase).
Start of manual or automatic battery test.
Rectifier output voltage is decreased to the value defined
by parameters.
End of manual or automatic battery test.
Rectifier output voltage is restored to floating voltage.
Rectifier received the command to switch ON
Rectifier received the command to switch OFF for:
input mains out of tolerance / EPO / UDC max.
Customer interface (X1 - 11, 22) received a Gen-set ON
signal. Operating mode depend on setting of parameters.
Customer interface (X1 - 11, 22) received a Gen-set OFF
signal. Function Bypass enabled depends on setting of
respective parameter.
Inverter cannot be switched on because one of the
following conditions is still present:
Overtemperature.
-
Low battery voltage.
-
Inverter fuses.
-
Overload.
-
K7 opening failure.
-
High battery voltage.
-
DC low.
-
EPO.
-
Inverter cannot be switched OFF, because the load cannot
be switched to mains (voltage out of tolerance, not
synchrony, BP blocked).
The command to start the inverter has been activated on
the control panel.
The command to switch OFF the inverter has been
activated by the control panel or automatically for alarm
presence.
Bypass input mains is again within tolerance (voltage,
frequency and phase).
Disconnection of the load by opening K6 and K7 for:
EPO / Load Off / Overload / Stop operation
With the load supplied by electronic bypass, a mains failure
or K6 opening occurred.
2 transfers inverter- mains has been detected in a short
time, defined by parameter (default 30 sec.).
Bypass to mains not enabled due to settings of parameters.
Contactor K6 is open.
Settings of parameters enable Bypass transfer on mains.
Contactor K6 can be closed.
Key "Load Off" on the UPS Control Panel has been pressed,
with the output circuit breaker Q1 closed.
Meaning
Operating Manual SitePro 10-15-20-30-40 kVA / S8
Page 52/99