Automatic Bypass; Manual Bypass - GE 8 Series Operating Manual

Table of Contents

Advertisement

4.2.5 Automatic Bypass

In normal operation, the Load is supplied by the
Inverter.
When the control system detects a fault in the
Inverter, an overload condition or a short-circuit
condition, the Automatic Bypass will transfer the
critical Load to the Mains without interruption.
When the Inverter recovers, or the overload or
short-circuit condition is corrected, the Load will
be automatically transferred back to the
Inverter.
If the UPS is unable to return to normal mode
following an automatic transfer to Bypass mode,
an alarm condition will be initiated.
A Manual Bypass (operator initiated) will not be
considered as an alarm condition.
In case of parallel operation
Each unit has its own internal Bypass.
These units are continuously exchanging information, enabling all of the internal Bypass circuits in a
Parallel System to operate simultaneously.
If the Inverter of a unit fails, its Bypass circuit remains available to the Parallel System.
It is excluded only if the unit is separated from the common bus by opening its output switch Q1.

4.2.6 Manual Bypass

The Manual Bypass circuit consists of manual
switches Q1 and Q2, which permits transfer of
the Load directly to the unconditioned AC power
without interruption, leaving the UPS available
for maintenance.
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Fig. 4.2.5-1 Block diagram Automatic Bypass
Fig. 4.2.6-1 Block diagram Manual Bypass
Operating Manual SitePro 10-15-20-30-40 kVA / S8
Page 15/99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents