Siemens SIRIUS 3RW5 series Manual page 97

Soft starters and solid-state switching devices modbus tcp communication module
Hide thumbs Also See for SIRIUS 3RW5 series:
Table of Contents

Advertisement

Register Byte
Data format
[Obj. No.]
Address high / low
0x9449
high
Unsigned32
[2224]
0x944B
high
Unsigned32
[2225]
0x944E
high
Bool
[34]
0x944F
high
Bit32
[35]
0x9452
high
Bit2
[140]
0x9453
high
Bit4
[232]
0x9454
high
Bit4
[129]
0x9455
high
Bit4
[2344]
low
Bit4
[2345]
0x9456
high
Unsigned8
[2346]
low
Unsigned8
[2347]
0x9457
high
Unsigned16
[2352]
SIRIUS 3RW5 Modbus TCP communication module
Manual, 03/2018, A5E43676481002A/RS-AA/001
Parameters
Analog output - range start
value
Analog output - range end
value
Response to CPU/Master
Stop
Substitute value
Response to overload
switching element
Response to faulty main
power
Response to preset unequal
actual configuration
Pump cleaning mode
Pump cleaning - start/stop
parameters
Pump cleaning - time
Pump cleaning - cycles
Current limiting value -
automatic parameterization
Range of values
[encoding]
0 ... 4 294 967 295
[0 ... 4 294 967 295]
0 ... 4 294 967 295
[0 ... 4 294 967 295]
[0 ... 1]
[0] Switch substitute
value
[1] Keep last value
-
[0 ... 1]
[0] Turn off without
restart
[1] Turn off with restart
[1 ... 2]
[1] Group error only at
ON command
[2] Warn
[0 ... 4]
[0] Turn off
[1] Warn
[4] Ignore
[0 ... 1]
[0] Deactivated
[1] Manual
[1 ... 5]
[1] Parameter set 1
[2] Parameter set 2
[3] Parameter set 3
[5] Operating parameters
0 ... 30 s
[0 ... 30]
0 ... 10
[0 ... 10]
125 ... 800 %
[125 ... 800]
Appendix
A.2 Data tables
Increment
3RW
52
55
1)
2)
[D*]
[D*]
1
r
r/w
[0]
[0]
1
r
r/w
[96]
[27 648]
-
-
r/w
[0]
-
-
r/w
[0]
-
r
r/w
[0]
[0]
-
-
r/w
[1]
-
-
r/w
[0]
-
-
r/w
[0]
-
-
r/w
[5]
1 s
-
r/w
[20]
1
-
r/w
[3]
1 %
-
r/w
[400]
97

Advertisement

Table of Contents
loading

Table of Contents