Communication Parameters; A.2.19 Communication Parameters - Siemens SIRIUS 3RW5 series Manual

Soft starters and solid-state switching devices modbus tcp communication module
Hide thumbs Also See for SIRIUS 3RW5 series:
Table of Contents

Advertisement

A.2.19

Communication parameters

Read access (r) to the communication parameters is possible via Function Codes 03 and 04.
Write access (w) is possible for individual communication parameters via function codes 06
and 16.
Register
Byte
Data format
Address
high / low
0xA102
high
Unsigned32
-
-
Unsigned32
0xA10E
high
low
0xA10F
high
low
-
-
Unsigned32
0xA110
high
low
0xA111
high
low
-
-
Unsigned32
0xA112
high
low
0xA113
high
low
0xA114
high
OctetString6
SIRIUS 3RW5 Modbus TCP communication module
Manual, 03/2018, A5E43676481002A/RS-AA/001
Parameters
Access monitoring time
IP address
(Byte3.Byte2.Byte1.Byte0)
Byte 3
Byte 2
Byte 1
Byte 0
Subnet mask
(Byte3.Byte2.Byte1.Byte0)
Byte 3
Byte 2
Byte 1
Byte 0
Address of router
(Byte3.Byte2.Byte1.Byte0)
Byte 3
Byte 2
Byte 1
Byte 0
MAC address
Range of values
[encoding]
[5 000 ... 10 000]
[5 000] 5 s
[10 000] 10 s
-
[0 ... 255]
[0 ... 255]
[0 ... 255]
[0 ... 255]
-
[0 ... 255]
[0 ... 255]
[0 ... 255]
[0 ... 255]
-
[0 ... 255]
[0 ... 255]
[0 ... 255]
[0 ... 255]
-
Appendix
A.2 Data tables
Default
Access
5 000
r/w
-
-
192
r/w
168
r/w
42
r/w
99
r/w
-
-
255
r/w
255
r/w
255
r/w
0
r/w
-
-
0
r/w
0
r/w
0
r/w
0
r/w
-
r
99