Hysteresis Limit - ProMinent DULCOMETER Assembly And Operating Instructions Manual

Compact controller ph/redox measured variable
Table of Contents

Advertisement

8.4

Hysteresis limit

Measured value
Upper
limit value
"Hysteresis"
"Hysteresis"
Lower
limit value
Limit value
transgression
Fig. 35: Hysteresis
Upper limit value = LIMIT↑
Lower limit value = LIMIT↓
The range between LIMIT↑ and LIMIT↓ is the valid measuring range.
The DULCOMETER
Measured variable
pH
Redox
'Hysteresis' acts to cause an increase in the limit value transgression, i.e. if the
The
'Limit↑ ' of e.g. pH 7.5 was exceeded, then the criterion for a limit value transgression is
only removed again when the value falls below pH 7.22. The hysteresis behaviour for a
'Limit↓ ' functions in an analogue way (the hysteresis value is here added to the
Limit↓ ), for example
gression criterion is only removed again when the pH exceeds 4.28.
®
Compact Controller has fixed
'Limit ↓ ' pH 4.00, hysteresis pH 0.28, then the limit value trans‐
Control parameters and functions
'hysteresis' .
Hysteresis
0.28 pH
20 mV
t
t
A0009_GB
73