Setup Options; Surge Protection Option - Eaton Powerware Series User Manual

Hide thumbs Also See for Powerware Series:
Table of Contents

Advertisement

OPERATION
Table 8. Setup Options
Minimum
Description
Level*
0
Enter Password
0
Versions
0
Contrast Adjust
1
Log Out
1
Change Access Level Password
1
Set Date and Time
1
Clear History
1
Clear Load Profile
1
THD Alarm Level
2
Unit Type
2
Unit Name
2
Reset All lower Level Passwords
* Minimum System Setup Level required to access the setup option.

Surge Protection Option

38
EATON Power Distribution Rack (208V) User's Guide

Setup Options

Access to setup options is restricted to three System Setup Levels: 0, 1, or 2. The
higher the level, the more setup options are available. Options on System Setup
Level 0 do not require password access.
Available Settings
Use the arrow keys to enter the password for the level you want to
access, then select DONE to display the options for the setup level.
Read only
Adjust screen contrast with left/right arrow buttons
Exit the Level 1 or Level 2 setup options and display the Level 0
setup options
Change the password for the current setup level
Use the arrow keys to enter the new password (A–Z, 0–9, –, blank),
then select DONE to save the new password.
Set Month, Date, Year (mm/dd/yyyy)
Set Hour, Minute (Time is a 24−hour clock.)
Clear the History Log
Clear the Load Profile
Set the voltage and current Total Harmonic Distortion for Input 1
and Input 2, and enable or disable this feature:
THD settings
Enabled/Disabled
Read only: Model / CTO / Serial
Up to 20 characters (A–Z, 0–9, –, blank)
Reset the Level 1 password to the default setting
The optional Transient Voltage Surge Suppression / Surge Protective Device
(TVSS/SPD) has three status indicators (see Figure 23) visible through a slot near the
bottom of the interior barrier protecting the panelboard. The PDR provides up to four
TVSS/SPD devices, depending on configuration. For TVSS/SPD specification details,
see Table 14 on page 44.
NOTE Phase status generated by the TVSS/SPD is communicated through the TVSS/SPD status indicators,
not through the display.
S
164201720 Rev 1 www.powerware.com
POWER APPLIED TO PHASES
(green indicators illuminated)
Figure 23. TVSS/SPD Indicators
Default Setting
Level 1: L1
Level 2: Contact your service
representative
Current firmware versions
installed
10%
None
None
00/00/0000
00:00
None
None
5.0
Disabled
Factory−set identifiers
EATON EMS−PDR
None