Page 1
Powerware Series ® ® Eaton FERRUPS Rack Mount UPS User's Guide...
Page 3
Powerware Series ® ® Eaton FERRUPS Rack Mount UPS User's Guide...
Page 4
Inc. WYSE is a registered trademark of WYSE Technology Inc. All other trademarks are property of their respective companies. ECopyright 1997–2010 Eaton Corporaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
Provides regulated output voltage without drawing power from batteries, keeping the batteries fully charged from unexpected blackouts. Complete offering of power management software included to ensure data integrity. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Proper disposal of batteries is required. Refer to your local codes for disposal requirements. Never dispose of batteries in a fire. Batteries may explode when exposed to flame. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 10
Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer. Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved åben ild. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 11
Houd onbevoegden uit de buurt van de accu's. De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 12
Älä päästä valtuuttamatonta henkilöstöä lähelle akkuja. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 13
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 14
Vorsichtsmaßnahmen verfügt. Nicht autorisiertes Personal von Batterien fern halten. Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen Bestimmungen zu beachten. Batterien niemals verbrennen, da sie explodieren können. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 16
Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 17
Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier. Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 18
Siga as instruções apropriadas ao desfazer‐se das baterias. Consulte os códigos do local para maiores informações sobre os regulamentos de descarte de produtos. Nunca jogue as baterias no fogo, porque há risco de explosão. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 20
Para cumplir con los estándares internacionales y las normas de instalación, la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 1,5 miliamperios. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 21
För att överensstämma med internationell standard och installationsföreskrifter får inte den totala utrustning som anslutits till uttagen på denna UPS-enhet ha läcksström som överstiger 1,5 milliampere. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 22
Håll ej behörig personal borta från batterierna. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Identifying Your UPS NOTE Before starting up the UPS, verify that it has been installed according to the Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) Installation Guide. FERRUPS Rack Mount UPSs come in different sizes (see Figure 1).
For Plug-Receptacle UPSs: Plug the UPS power cord into a power outlet. NOTE If the plug does not match your receptacle outlet, ask your electrician to install the proper outlet. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 25
If the CHARGING indicator is illuminated, operate the UPS for 24 hours to fully charge the battery. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1...
Page 26
(Ah) for the total number of battery packs used in the UPS. If you purchased one of the FERRUPS Rack Mount battery pack options available from Eaton, select the Ah value from Table 1. NOTE A Remote Control Panel (part number RCK-0007), PC, or terminal is required to communicate with the UPS.
Confirm that your AC line disconnect switch and the UPS ON/OFF switch are both in the OFF position. If you have an RBC-1 or RBC-2 battery cabinet, skip to Step 4. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 28
UPS switches from battery power to AC input power. The BATTERY POWER indicator turns off. ALARM AC LINE READY CHARGING BATTERY POWER Figure 6. Front Panel Indicators Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 29
To set the time (in 24-hour format), follow these steps: Press this key: Display shows: Display: [DISPLAY] Display: 00 Time: 11:30:20 [ENTER] 00 Pgm: [PROGRAM] Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 30
(Ah) for the total number of battery packs used in the UPS. If you purchased one of the FERRUPS Rack Mount battery pack options available from Eaton, select the Ah value from Table 2. Before programming the battery Ah, enter the user-level password following the instructions in “Entering Passwords”...
Figure 8 shows the UPS front panel indicators. Table 3 explains the status of each indicator. ALARM AC LINE READY CHARGING BATTERY POWER Figure 8. Front Panel Indicators Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 34
(see “Alarms” on page 61). If you have a control panel, an alarm message appears on its display. No alarm exists. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Notice that names of the operating modes appear in red on the bottom of keys 1–4. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
FERRUPS [CLEAR] Password: [PROGRAM] Password: [3] [7] [7] Level: User [ENTER] Password Cleared To clear the password, press [CLEAR] until appears on the control panel display. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
To disable the panel, press the keys shown in the following example (verify that you have the necessary code to unlock the control panel). Press this key: Display shows: −Keypad Locked− [CLEAR] and [ENTER] together Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
If not, the UPS sounds alarm M, Check Battery ( ). See page 63. The READY indicator flashes – – during this part of the test. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
When this value drops below the brownout voltage, the UPS switches to inverter. 02 V Out 120.7 Service acvoltsout The voltage the UPS is providing to your (vo) equipment. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 41
12 SinkTemp 26c Change Not heatsinktemp The temperature of the heatsink. The UPS Allowed (st) sounds an alarm if this value is too high. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 42
UPS ON/OFF switch is in the OFF position. 23 InvMin 0000.0 Change Not invmin The total number of minutes the inverter Allowed (im) has run since startup. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
When it has gone into the Off mode because the batteries have been discharged during an extended outage. When a system malfunction requires a UPS shutdown. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 44
Use the FERRUPS key to turn the UPS ON/OFF switch to the OFF position. If the UPS is plugged in, unplug it. For hardwired models, turn the AC line disconnect switch to the OFF position. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
If your UPS shuts itself down because its battery voltage is too low, shut down the UPS until the AC input power returns (see “UPS Shutdown” on page 37). Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
UPS Low Battery shutdown occurs. NOTE You can download the latest software version from www.eaton.com/powerquality. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1...
6 or 18) is for remote shutdown. The following sections describe how to take advantage of these features. Pin 20 is for option use only. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
RS-232 port to your terminal or computer, you need a cable designed specifically for this purpose (see Figure 11 and Figure 12). Eaton offers cables for computers or terminals using 25-pin or 9-pin serial ports; call your service representative to order one of these cables.
Page 50
Table 7 shows the standard settings at the UPS DB-25S port and the settings that can be adjusted. Call your service representative if you need to adjust any of the settings. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 51
Key Sequence Delete last character typed. [BACKSPACE] or [CTRL]-[H] Delete line. [CTRL]-[X] Pause displays that take more than one screen. [CTRL]-[S] Resume scrolling. (Turn Pause off.) [CTRL]-[Q] Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
*If you change parameter 39 to “Yes,” this command requires a user-level password. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 53
UPS shortly after power returns. off cancel None* Cancels timed shutdown. *If you change parameter 39 to “Yes,” this command requires a user-level password. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 54
Enters the Off mode. In this mode, the UPS is not providing power to your equipment, but you can still use the UPS control panel. *If you change parameter 39 to “Yes,” this command requires a user-level password. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Contacts that close on inverter operation are available between Pins 12 and 13. Contacts that open on inverter operation are available between Pins 11 and 13. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
You can also set up the UPS to restart automatically when the shutdown signal stops. See TIP 503 or contact your service representative for more information. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Chapter 6 Options Eaton offers many options for your FERRUPS Rack Mount UPS. If you would like more information, contact Eaton or your local distributor. Bypass Switches If your UPS does not have a plug, a bypass switch can transfer the protected equipment to direct AC input power conveniently when it's time to service the UPS.
Check and record the values of the first 19 parameters while the UPS is online and on battery. For more information on preventive maintenance checks, contact your service representative. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Other voltages available. Contact Eaton or your local distributor. 120 Vac is optional for FER 4.3 kVA and FER 7 kVA models. At 0.7 leading power factor. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 62
National Electrical Code Article 250-5d, with output neutral bonded to ground. There is no direct connection between input and output, and less than 2 pF of effective input to output capacitance. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 63
Standard batteries are sealed, gas recombinant, lead-acid type, especially designed for UPS use. NOTE Optional battery chargers at higher current ratings are available. Contact Eaton or your local distributor for more information. Table 14. Battery Times (in Minutes) 850 VA/ 1.15 VA/...
Page 64
(35.6 cm x 48.3 cm) RBC-3 Battery Cabinets 8.3I x 16.25I x 24.25I 8.8I x 19.0I (21.1 cm x 41.3 cm x 61.6 cm) (22.4 cm x 48.3 cm) Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 65
103 kg — QFER 3.1 kVA 66 kg 111 kg — QFER 4.3 kVA 118 kg — 113.4 kg QFER 7 kVA 158.8 kg — 113.4 kg Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
NOTE If you do not turn the alarm beep back on, the UPS is not able to sound an alarm code the next time there is an alarm. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1...
Page 68
If not, shut down Temp the UPS shuts down. your equipment or bypass the UPS; turn the UPS off. Contact your service representative. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 69
Contact your service representative. Input setting. – Call Service The UPS has detected a problem that The UPS shuts down. Contact your requires service. service representative. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
(*) after “B.” “0205” means the alarm occurred on February 5 (2/5). “1017” means the alarm occurred at 10:17 a.m. “0005” means the alarm condition lasted for 0 hours and 5 minutes. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
AC input power was lost. Manual The inverter was started manually. Frequency Input frequency was too high or too low. Reset A system reset was performed. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
UPS ran on battery power (Duration), and the reason (Code/Event). You can also display parameter 24 to view the Inverter Log; this display is the same as the control panel display. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
A replacement or repair unit will be shipped, freight prepaid for all warrantied units. NOTE For critical applications, immediate replacement may be available. Call the Help Desk for the dealer or distributor nearest you. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Eaton 9120, 9125, 9130, 9135, 9140, and FERRUPS up to 3.1 kVA Products (individually and collectively, the “Product”) purchased on or after June 1, 2004, and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-User.
Page 76
END-USER'S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must use the Product in a normal way; follow the Product's user's guide; and protect against further damage to the Product if there is a covered defect. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, contact your local Eaton product sales or service representative. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
Page 78
CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN “OPEN SOURCE” MODEL OR IS DISTRIBUTED PURSUANT TO AN OPEN SOURCE LICENSE. Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1 www.eaton.com/powerquality...
Page 79
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, contact your local Eaton product sales or service representative. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
LIMITED GUARANTY: This load protection guaranty (this “Guaranty”) applies only to the original End-User (the “End-User”) of any Eaton 3105, 5110, 5115, 5125, 5130, 9120, 9125, 9130, 9135, 9140, 9150, 9155, 9170+, and FERRUPS Products (individually and collectively, the “Product”) and cannot be transferred. This Guaranty applies even in the event that the Product is initially sold by Company for resale to an End-User.
Page 81
TO MAKE A CLAIM: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, contact your local Eaton product sales or service representative. For comments or questions about this Load Protection Guaranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
Page 84
Alarm Code Summary See “Troubleshooting” on page 61 for more information. – Low Battery – – Hi Transfmr Temp S S S – Near Low Battery – Check Charger – – High Battery – – Check Battery – Low Runtime –...
Need help?
Do you have a question about the Powerware Series and is the answer not in the manual?
Questions and answers