Powerware Series ® Eaton 9170 Battery Charger Module Models ASY-0652 and ASY-0675 User's Guide...
Page 2
Eaton and Powerware are registered trademarks of Eaton Corporation or its subsidiaries and affiliates. All other trademarks are property of their respective companies. ECopyright 2002–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
12 kVA Capacity 18 kVA Capacity Number of Designed Battery Runtime Battery Recharge Battery Recharge Battery Recharge Charger (Minutes) Modules Time (Hours) Modules Time (Hours) Modules Time (Hours) Modules Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Besides input power, the external battery cabinet has a cable or conduit connection to the UPS cabinet. It may also have a cable or conduit to additional external battery cabinets. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E...
Page 7
INTRODUCTION To UPS or Previous External DC Disconnect Switch Battery Cabinet Button AC Line In To Next External Battery Cabinet Figure 2. External Battery Cabinet for Charger Modules Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
For optimum charging of batteries, you must set DIP switches 1 and 2. Follow the guidelines in Table 3 to determine the proper output current setting and set DIP switches 1 and 2 accordingly (see Figure 4). Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
30 days, set DIP switch 3 to ON. NOTE Enable only one Battery Charger Module in external battery cabinets. Reserved Switch The function of DIP switch 4 is reserved; it should remain in the OFF position. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Be sure the handle latch snaps into place. Tighten the thumbscrew on the handle. Reinstall the front cover(s). Turn on the UPS according to the UPS user's guide. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Output current is controlled by power modules on the UPS CAN bus or by the rear panel DIP switches. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
3/2100 30/29.5/29/28.5/28A 15/14.5/14/13/12.5A 570W (1.95 kBTU/hr) * Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet ASY-0739. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Page 16
102A* 45/43.5/42/39/37.5A 125A 1995W (6.75 kBTU/hr) * Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet ASY-0739. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Page 17
100/97/94/91/88A* 90/87/84/78/75A 125A 1995W (6.75 kBTU/hr) * Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet ASY-0739. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Page 18
15A, 14A, 12.5A 1145W (3.90 kBTU/hr) * Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet ASY-0739. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Page 19
60A, 56A, 50A 100A 1430W (4.88 kBTU/hr) * Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet ASY-0739. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Page 20
15A, 14A, 12.5A 285W (0.98 kBTU/hr) * Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet ASY-0739. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Page 21
30A, 28A, 25A 860W (2.93 kBTU/hr) * Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet ASY-0739. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Page 22
75A, 70A, 62A 125A 1720W (5.85 kBTU/hr) * Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet ASY-0739. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Page 23
90A, 84A, 75A 125A 1995W (6.75 kBTU/hr) * Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet ASY-0739. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Shorted output error Call your service representative. 1 short, pause, 3 short Battery overvoltage error Call your service representative. 1 short, pause, 4 short Charger failure Call your service representative. Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
Raise the Battery Charger Module handle to secure the module into the cabinet. Be sure the handle latch snaps into place. Tighten the thumbscrew on the handle. Reinstall the front cover(s). Eaton 9170 Battery Charger Module User's Guide 164201399 Rev E www.eaton.com/powerquality...
TROUBLESHOOTING Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Eaton Customer Support Center at one of the following telephone numbers. Available Support Services: Onsite Service Technician scheduling Technical product information or troubleshooting...