Rosemount 3051S Series Pressure Transmitter
November 2017
Figure 1. Transmitter Data Flow
Measured
process
input
1.1

Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance
with local and national legislation/regulations.
2.0
Configuration
For complete configuration details using Fieldbus, reference the
Fieldbus Reference Manual.
2.1

Device configuration

Display configuration

The following configuration items are found in the LCD display Transducer Block.
The transmitter features a three-line display. The first line of five characters displays the output
description, the second line of seven digits displays the actual value, and the third line of six characters
displays engineering units. The LCD display meter can also display diagnostic messages.
Each parameter configured for display will appear on the LCD display for a brief period before the next
parameter is displayed. Up to four different variables may be shown on the display.
The LCD display meter is preconfigured to show the measured variables that correspond to the
transmitter configuration. It can be configured to display any measured or calculated value that has a
status parameter with it (i.e. F
display as stated below.
Display parameter select
The display of each configured parameter can be turned on or off by editing the Display Parameter Select
parameter. Parameter options include pressure, module temperature, bar graph, and scaled variable.
Note
The scaled variable configuration allows the user to create a relationship/conversion between the pressure units and
user-defined/custom units.
Block type
Enter the Block Type for the block that contains the parameter to be displayed.
Block tag
Enter the Block Tag of the block that contains the parameter to be displayed.
2
P
A/D
OUNDATION
Micro
FF communications output
Fieldbus DS-65 parameter type). Configure each parameter for
Manual Supplement
00809-0200-4853, Rev AB
Rosemount 3051S F