Rosemount 3051S Series Pressure Transmitter
November 2017
Table 6. Failure–Fix Now
Alert label
Sensor Module
Failure
Sensor Module
Communication
Failure
Sensor Module
Incompatibility
Table 7. Out of Specification–Fix Soon
Alert label
Pressure Out of
Limits
Module
Temperature
Out of Limits
Table 8. Maintenance Required
Alert label
Plugged
Impulse Line
Detected
Statistical
Process
Monitor Trip
8
LCD
display
Description
message
FAIL
Failure has been
SENSOR
detected in the sensor
module
ERROR
Electronic circuit board
SNSR
has stopped receiving
COMM
updates from the sensor
ERROR
module
SNSR
Sensor module is not
INCOMP
compatible with the
electronic circuit board
ERROR
LCD
display
Description
message
Pressure has
exceeded the
PRESS
transmitter's
LIMIT
maximum
measurement range
Module temperature
SNSRT
sensor has exceeded
LIMIT
its normal range
LCD
display
Description
message
Plugged impulse
line has been
ADB
detected by the
ALERT
Advanced
Diagnostics Block
Statistical process
monitor has
detected either a
ADB
mean variation or
ALERT
high or low
dynamics in the
process
Recommended action
1. Replace the sensor module.
1. Verify the device is receiving adequate supply
voltage.
2. Remove front housing cover (considering
hazardous location requirements) and check
the cable and cable connection between sensor
module and electronic circuit board.
3. Replace the electronic circuit board.
4. Replace the sensor module.
1. Replace the sensor with a compatible single
variable sensor module.
Recommended action
1. Verify conditions of the process where the
transmitter is installed.
2. Check transmitter pressure connection to make
sure it is not plugged and isolating diaphragms are
not damaged.
3. Replace the sensor module.
1. Check process and ambient temperatures where
the transmitter is installed to ensure they are
within specifications.
2. Replace the sensor module.
Recommended action
1. Verify there is a plugged line.
2. If this is a false trip, reconsider the trip values and
restart the diagnostic.
1. Verify the condition of the process being monitored by
the SPM.
2. If this is a false trip, reconsider the SPM configuration.
Rosemount 3051S Series Pressure Transmitter
Manual Supplement
00809-0200-4853, Rev AB