Issue 04/02
Motor data for parameterization
Figure 3-7
NOTICE
P0308 & P0309 are only visible if P0003 ≥ 2. Only one of the parameters are
shown depending on the settings of P0100.
P0307 indicates kW or HP depending upon the setting of P0100. For detailed
information, please see the Parameter List.
Changing motor parameters is not possible unless P0010=1.
Ensure that the inverter is configured correctly to the motor, i.e. in the above
example delta terminal connection is for 230 V.
3.2.3.2
Reset to Factory default
To reset all parameters to the factory default settings; the following parameters
should be set as follows (BOP, AOP or Communication Option needed):
1. Set P0010 = 30
2. Set P0970 = 1
NOTE
The reset process can take up to 3 minutes to complete.
MICROMASTER 420
Operating Instructions
6SE6400-5AA00-0BP0
P0308 P0310
P0304
50 Hz
230/400V
0.61 0.35 A
Cos
0.81
0.12kW
j
2800 / min
65%
P0309
P0305 P0311 P0307
Typical Motor Rating Plate Example
3_Mot
Nr. ED510 3053
IEC 56
IP54
Rot KL 16
IM B3
60 Hz
440V Y
0.34A
0.14 kW
Cos
0.81
j
3310 /min
S.F. -- 1.15
3 Commissioning
12.022
I.CI.F
43