Auxiliary Contact Installation; Auxiliary Contact Wire Routing; Line Terminal Adapter Installation; Electrical Interlock Installation - Allen-Bradley A Series Installation Instructions Manual

Universal disconnect switch
Hide thumbs Also See for A Series:
Table of Contents

Advertisement

Auxiliary Contact Installation

1
1
#18 - #12 AWG
(0.75-2.5 mm²)
6-8 lb-in
(0.7-0.9 N-m)
2

Line Terminal Adapter Installation

Adapter
90-105 lb-in
(10.2-11.9 N-m)
Wire Clamp Range
(1) 14-10 STR/SOL
(1) 8 STR
(2) 14 SOL/SOL
(2) 14 STR/STR
(2) 12 SOL/SOL
(2) 12 STR/STR
(2) 10 SOL/SOL
(2) 10 STR/STR
(2) 8 STR/STR
0.32"
(8 mm)
2
CLICK
NOTE:
USE ADAPTER ON
LINE SIDE ONLY
Publication 1494U-IN007B-EN-P - July 2018
Universal Disconnect Switch Installation Instructions (200A)

Auxiliary Contact Wire Routing

Wire routing channel

Electrical Interlock Installation

Wire Clamp
25 lb-in
(2.8 N-m)
Wire
Lug
25 lb-in
(2.8 N-m)
Wire tie-down points
Wire
Range
Torque
6.9-10.4 lb-in
18-12 AWG
(.78-1.18 N-m)
9