4
Universal Disconnect Switch Installation Instructions (200A)

Cable Operated Switch Installation

1
1494U Handle and Cable Mechanism Installation
Enclosures with Right Flange
1
Connect handle link to lever pin.
Lever Pin
2

Cable to Switch Mechanism Installation

IMPORTANT: Verify that the cable assembly does not interfere with any mechanical and moving parts. Keep the cable conduit away from all heat sources and current carrying terminals,
fuses, transformers, etc.
1
Tighten cable nuts onto switch bracket.
NOTE: Ensure there is one
washer on each side
of the switch bracket.
3/8" (9.5mm)
Top of thread to
top of upper nut.
3
Assemble washers (2) and hitch pin to attach cable pivot to switch mechanism cable slot.
2
Install handle nuts and hitch pin.
30-40 lb-in
(3.4-4.5 N-m)
Handle Link
Switch
Bracket
75-90 lb-in
(8.5-10.2 N-m)
1
2
ATTENTION:
If not operating properly, go to Cable Operated
Adjustment Procedure.
Publication 1494U-IN007B-EN-P - July 2018
2
Ensure switch is located as to not pinch the cable or create a bend less than 6" in
diameter.
6" Diameter
Min.
CHECK FOR PROPER OPERATION.
3
Install defeater lever.
OFF
7-11 lb-in
(0.8-1.2 N-m)
Install pin as shown.
Do not push past
second bend on clip.
Defeater
Lever