Rod Operated Adjustment Procedure; Cable Operated Adjustment Procedure - Allen-Bradley A Series Installation Instructions Manual

Universal disconnect switch
Hide thumbs Also See for A Series:
Table of Contents

Advertisement

Rod Operated Adjustment Procedure

Adjustment Procedure if switch does not turn "ON".
1
Move disconnect handle to the "ON" position.
2
If switch does not fully close, return handle to "OFF" position.
3
Remove link spring and hitch pin to disengage the connecting
rod from the primary link.
4
Turn connecting rod counter-clockwise (1 or more) full turns.
5
Re-engage connecting rod in primary link of handle, insert hitch
pin and re-test.
-
Repeat
as necessary.
6
1
5
Re-install link spring.
7

Cable Operated Adjustment Procedure

1
Move handle to "ON" position.
4
(a) ADJUSTMENT PROCEDURE IF SWITCH
DOES NOT FULLY CLOSE.
Unscrew clevis ONE full turn counter-
clockwise to extend cable.
Universal Disconnect Switch Installation Instructions (200A)
Adjustment Procedure if switch does not turn "OFF".
1
Move disconnect handle to the "OFF" position.
2
If switch does not fully close, return handle to "ON" position.
3
Remove link spring and hitch pin to disengage the connecting rod
from the primary link.
4
Turn connecting rod clockwise (1 or more) full turns.
5
Re-engage connecting rod in primary link of handle, insert hitch pin and
re-test.
Repeat
6
Re-install link spring.
7
2
Remove hitch and clevis pins.
Clevis Pin
Clevis
4
(b) ADJUSTMENT PROCEDURE IF SWITCH
DOES NOT FULLY OPEN.
Turn clevis ONE full turn clockwise to
shorten cable.
Publication 1494U-IN007B-EN-P - July 2018
-
as necessary.
1
5
3
Return handle to "OFF" position.
Hitch Pin
5
Return handle to "ON" position. Reinstall
clevis, clevis pin and hitch pin.
6
Confirm switch operates properly and
repeat steps 2-5, if necessary.
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1494u-d200

Table of Contents