6
Universal Disconnect Switch Installation Instructions (200A)

Enclosure without Handle Cutout

• Some Enclosures with hinged flange panels may require additional flange support brackets to stiffen panel.
Consult your local enclosure manufacturer.
1
Locate Handle
Door Catch
Mounting
Bracket

Door Catch Bracket Installation

Right hand installation shown (for left hand installation follow similar procedures)
Door Catch Mounting Bracket:
• Provided with projections for welding.
• Projections can also be used as a guide for drilling holes in the enclosure door.
• User to supply the hardware for fastening the bracket.
• The bracket hardware must be inaccessible to unauthorized personnel.
• Fasteners must provide the degree of ingress protection for the environmental rating of the enclosure.
Dimension K (3/4" to 1")
• When using small disconnect handle kit only (1494U-HP1, -HM1 or -HS1), use door catch provided with handle kit.
• When using small disconnect handle kit and small door hardware kits (1494V-L1, -LL1, -L2 or -LL2), use door catch
provided with door hardware kit.
Dimension K (1-1/8" to 1-3/8")
• When using small disconnect handle kit only (1494U-HP1, -HM1 or -HS1), use door catch (40492-080-02) which can be
ordered from factory.
• When using small disconnect handle kit and large door hardware kits (1494V-L3 or -LL3), use door catch provided with
door hardware kit.
Door Catch
Mounting Bracket
22-37 lb-in
(2.5-4.2 N-m)
1-3/32 MAX.
1-1/4" MIN.
10-1/8"
MIN.
2-3/8"
1-5/8"
Right hand flange shown. Mirror for left hand flange.
Top
Publication 1494U-IN007B-EN-P - July 2018
Top Handle Hole
To make slot, drill (3)
1/2" diameter holes
and remove burrs.
TOP VIEW
Door Catch
Mounting
Bracket
Door Catch
2
Drill Handle Holes
(2) .265 Dia. Holes
1-9/16"
1"
7/8"
1"
Enclosure Door
Flange
Thickness
1-3/32"
Enclosure
Base
1-1/4"
1-5/8"
4-11/16"
K