ambient climate automatic control in the temperature controls. The controls may be
used both for internal channels and for other heating/cooling actuators.
Use channel 1...8
Use temperature control 1...4
4.3.

Channel 1...8

Use the channel menus to select the controls for the heating or cooling system
connected to the respective output channel.
First, select the type of valve, then the valve protection interval. This is the interval
after which the valve is opened and closed once to avoid jamming.
Valve type
Valve protection interval (days)
(0=deactivated)
Select the control type for the valve:
Control type
When controls are effected via a 1 bit object, fixed output values are selected for
1 (On) and 0 (Off);
Value of output when object value = 1
Value of output when object value = 0
When controls are effected via a 8 bit object, fixed output values are selected for "not
0 (On) and 0(Off);
Output value
if object value is not 0
Output value
if object value is 0
For controls via an 8 bit object with pulse width modulation (PWM), only the
basic time for the pulse width modulation is set (next setting).
If control takes place via one of the internal temperature controls, control and
variable are selected.
Temperature controller no.
KNX K8 actuator • Status: 18.11.13 • Technical Changes and Errors excepted.
11
Yes• No
Yes• No
• normally closed
• normally open
0...255; 14
• via object (1 bit)
• via object (8 bit ON | OFF)
• via object (8 bit PWM)
• via temperature controller
0...100
0...100
0...100
0...100
1 • 2 • 3 • 4
Parameter setting