KNX S1R-BA4-UP 24 V
Actuator for a 12-24 V DC motor
Item number 70516
Installation and Adjustment

Advertisement

Table of Contents
loading

Summary of Contents for elsner elektronik KNX S1R-BA4-UP

  • Page 1 KNX S1R-BA4-UP 24 V Actuator for a 12-24 V DC motor Item number 70516 Installation and Adjustment...
  • Page 3: Table Of Contents

    6.3.1. Temperature threshold value 1, 2, 3, 4 ............. 54 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Actuator KNX S1R-BA4-UP 24 V • from software version 4.00, ETS programme version 4.0 Status: 27.05.2020 • Subject to technical changes. Errors excepted.
  • Page 4 Clarification of signs Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician. This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service"...
  • Page 5: Description

    ETS online catalogue and the Elsner Elektronik website on www.els- ner-elektronik.de in the “Service” menu. 1.0.1. Scope of delivery • Actuator Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
  • Page 6: Technical Specification

    KNX +/- bus plug-in terminals BCU type Integrated microcontroller PEI type Group addresses max. 1024 Assignments max. 1024 Communication objects Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
  • Page 7: Installation And Commissioning

    No persons may remain in the travelling range of parts driven by an electric motor. • Adhere to the relevant building regulations. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
  • Page 8: Installation

    1: GND | 2: IN1 | 3: GND | 4: IN2 | 5: GND | 6: IN3 | 7: GND | 8: IN4 All GND connectors are internally bridged. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
  • Page 9: Connection

    The physical address is assigned by the KNX software. There is a button with a control LED for this on the actuator. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
  • Page 10: Connection Examples

    T-NTC temperature sensor on input 4. Connection of the temperature sensor is in- dependent of the polarity. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
  • Page 11: Instructions For Assembly And Initial Start-Up

    After use, the device must be disposed of or recycled in accordance with the legal reg- ulations. Do not dispose of it with the household waste! Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
  • Page 12: Transfer Protocol

    DPT_Scaling Channel A - Status object Output R-CT 1 Bit 1.xxx Channel A - Approach Input LSK- [1.1] 1 Bit position memory for DPT_Switch manual Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 13 DPT_Value_Temp value Channel A - Inside Output R-CT [1.1] 1 Bit temperature release status DPT_Switch Channel A - Shading object Input RWC- [1.1] 1 Bit DPT_Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 14 Channel A - Warm air intake Input RWC- [9.1] 2 Bytes outside temp. measurement DPT_Value_Temp value Channel A - Warm air intake Input RWC- [9.1] 2 Bytes blocking target value DPT_Value_Temp Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 15 DPT_Switch Channel A - Slave zero Output R-CT [1.1] 1 Bit position status DPT_Switch Channel A - Drive is moving Output R-CT 1 Bit 1.xxx Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 16 Channel A - Blocking 4 - Input RWC- [9.5] 2 Bytes Wind blocking DPT_Value_Wsp measurement value Channel A - Blocking 4 - Output R-CT [1.1] 1 Bit Wind blocking status DPT_Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 17 R-CT [1.1] 1 Bit DPT_Switch Channel A2 - Status Readable R-C- [1.1] 1 Bit DPT_Switch Channel A2 - Blocking Input RWC- [1.1] 1 Bit object DPT_Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 18 DPT_UpDown Input 2 - Switching Input / RWCT [1.1] 1 Bit Output DPT_Switch Input 2 - Relative dimming Input / RWCT [3.7] 4 Bit Output DPT_Control_Dimmin Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 19 DPT_UpDown Input 3 - Switching Input / RWCT [1.1] 1 Bit Output DPT_Switch Input 3 - Relative dimming Input / RWCT [3.7] 4 Bit Output DPT_Control_Dimmin Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 20 7.xxx Temp. threshold value 1: Output R-CT [1.1] 1 Bit Switching output DPT_Switch Temp. threshold value 1: Input -WC- [1.1] 1 Bit Switching output block DPT_Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 21 7.xxx Temp. threshold value 4: Output R-CT [1.1] 1 Bit Switching output DPT_Switch Temp. threshold value 4: Input -WC- [1.1] 1 Bit Switching output block DPT_Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 22: Parameter Setting

    (Channels are divided into two switches A1|A2): • General specifications for the switch function (see Output channel with drive, page 46) • Connecting different communication objects (see Connection (switch functions), page 51) Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 23: Channel Settings - Drives

    0 ... 600 positions in 10 ms (only for manual input) for slat movement from closed 0 ... 600 position in 10 ms (only for manual input) Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 24 (retracting when shading, closing windows). Perform a reference movement no • yes Perform a reference movement for more than 1 ... 255; 10 movements before an auto positioning movement Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 25: Control (Drives)

    (see graphic in chapter Connection options for zero position sensors in the general part). Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 26 (communication object). Use movement range limit Zero position sensor connected as • communication object • input channel Actuator is master • slave Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 27 • yes, as wind blocking • yes, as rain blocking Use block 4 • no • yes, with blocking object • yes, as wind blocking • yes, as rain blocking Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 28 (if "Expiration of a waiting period" was chosen) Switch to automatic for an object value 0 • 1 • 0 or 1 (if "Receipt of an object" was chosen) Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 29 Slat position in % (only if by using a block, 0...100 a specific shutter position is achieved) If blocking object has value =0 Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 30 For automatic operation after blocking follow automatic 16 bit input object: Type of input object 16 bit As of wind speed in m/s 2...30; 5 blocking Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 31 Behaviour after waiting period For manual operation before and after • no action blocking • move into last position For automatic operation after blocking follow automatic Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 32: Manual

    = 1, short-term = 1 Use learning object for new position no • yes Transfer when programming • all parameters (when learning object is used) • changed parameters only Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 33: Automation - External

    The time control is provided via a communication object. The input object "twilight control" is linked with the output object of a brightness sensor. A 1bit object (smaller Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 34 1 … 100; 20 Send current blocking status no • yes Shading is allowed if the measurement value is greater than or equal to the target value+difference Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 35 The threshold value is received via the communication object and can be changed additionally (e.g. button for "more sensitive" and "less sensitive"). Set the delay times Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 36 Azimuth from 0 … 360 Azimuth to 0 … 360 Elevation from 0 … 90 Elevation to 0 … 90 Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 37 Shutter position in % 0 … 100 Use teaching object for new shading no • yes position (only the curtain position will be saved, see info below) Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 38: Automatic For Windows (Drives)

    Ventilation is allowed if the measurement value is larger than the threshold value+hysteresis and blocked if the measurement value is smaller than or equal to the threshold value. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 39 Ventilation is allowed if the outdoor measurement value is smaller than the target value+difference-hysteresis and blocked if the outdoor measurement value is greater than or equal to the target value+difference. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 40 • not retained • after voltage returns • after voltage returns and programming Start threshold value in 0.1°C 100 … 500; 300 valid until 1st communication Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 41 If the ventilation is controlled by temperature and humidity via a 16bit input object, then you can either set an opening position or open the windows incrementally. In the Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 42: Scenes (Drives)

    Window position in % Slat position in % 0...100; 70 (only for shutters) 6.2.1.7.Button inputs (drives) Depending on the model, there are no inputs, two or four inputs. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 43 • send 0 • send 1 • do not send telegram Command when releasing the button • send 0 • send 1 • do not send telegram Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 44 If the input to the drive control is used via the bus, select the bus function "shutter", "awning", "blinds" or "window" and specify the button function and control mode. Function Shutter / blinds / awning / window Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 45 If the input is to be used as an 8bit encoder, select the "8 bit encoder" bus function and specify which value will be sent. Function 8 bit encoder Value 0...255 Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 46 Scene No. 0...127 The input can be blocked using a blocking object. For active blocking there is no bus communication. Use blocking object No • Yes Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 47 Control modi for drive control, page 47. The input can be blocked using a blocking object. No operation is possible for an active block. Use blocking object No • Yes Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 48: Output Channel With Drive

    Time between short and long 1...50; 10 in 0.1 seconds Repeat the step command every 0.1 s • every 2 sec; every 0.5 sec for a long button press Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 49 The drive moves as soon as the button is actuated and stops as soon as the button is released. Control mode Dead man's switch Behavior during button operation: Push button = Up or Down command Release button = Stop command Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 50: Connection Option For Zero Position Sensors

    IN 1 IN 1 Master command Master Slave Master zero position status Drive 1 Drive 2 Slave zero position status at channel A at channel B Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 51 Zero position reached IN 1 Master command Master Slave Master zero position status Drive 1 Drive 2 Slave zero position status at channel A at channel B Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 52: Output Channel With Switch Function

    Linking 217: Channel A1 Linking Input (from twilight sensor) 211: Channel A1 Feedback Output Block function 213: Channel A1 Relay Blocking object input (from smoke detector) Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 53: Channel Settings - Switch Functions

    AND or OR. E.g. a light can only be switched on if the button input is active AND twilight is active. Connection type AND • OR Value of the connection object 0 • 1 after bus voltage returns Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 54: On/Off Switch Delays, Time Switching (Switch Functions)

    Time basis 0.1 s • 1 s • 1 min • 1 h Time factor 4...255; 10 Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 55: Blocking Function (Switch Functions)

    If a button with switch function is assigned to the input, select the button function "Switch" and specify what happens when pressing/releasing the button and when to send. Button function Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 56: Temperature Threshold Values

    6.3.1. Temperature threshold value 1, 2, 3, 4 Threshold value: ------------------------------ Set the threshold values directly in the application program using parameters, or define them via the bus using a communications object. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 57 Set the behaviour of the switching output when a threshold value is exceeded/ undercut. The output switching delay can be set using objects or directly as a parameter. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 58 Switching output sends on change to 0 • Do not send message • If switching output = 0  send 0 Switching output sends on change and Send switching output status periodically Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 59 If switching output = 1 send 1 Switching output sends on change to 1 and periodically If switching output = 0 send 0 Switching output sends on change to 0 and periodically Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
  • Page 60 Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone +49 (0) 70 33 / 30 945-0 info@elsner-elektronik.de Germany +49 (0) 70 33 / 30 945-20 www.elsner-elektronik.de Technical support: +49 (0) 70 33 / 30 945-250...