6.3.1. Temperature threshold value 1, 2, 3, 4 ............. 54 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Actuator KNX S1R-BA4-UP 24 V • from software version 4.00, ETS programme version 4.0 Status: 27.05.2020 • Subject to technical changes. Errors excepted.
Page 4
Clarification of signs Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician. This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service"...
ETS online catalogue and the Elsner Elektronik website on www.els- ner-elektronik.de in the “Service” menu. 1.0.1. Scope of delivery • Actuator Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
KNX +/- bus plug-in terminals BCU type Integrated microcontroller PEI type Group addresses max. 1024 Assignments max. 1024 Communication objects Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
No persons may remain in the travelling range of parts driven by an electric motor. • Adhere to the relevant building regulations. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
The physical address is assigned by the KNX software. There is a button with a control LED for this on the actuator. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
T-NTC temperature sensor on input 4. Connection of the temperature sensor is in- dependent of the polarity. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
After use, the device must be disposed of or recycled in accordance with the legal reg- ulations. Do not dispose of it with the household waste! Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.0 • Technical changes and errors excepted.
DPT_Scaling Channel A - Status object Output R-CT 1 Bit 1.xxx Channel A - Approach Input LSK- [1.1] 1 Bit position memory for DPT_Switch manual Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 13
DPT_Value_Temp value Channel A - Inside Output R-CT [1.1] 1 Bit temperature release status DPT_Switch Channel A - Shading object Input RWC- [1.1] 1 Bit DPT_Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 14
Channel A - Warm air intake Input RWC- [9.1] 2 Bytes outside temp. measurement DPT_Value_Temp value Channel A - Warm air intake Input RWC- [9.1] 2 Bytes blocking target value DPT_Value_Temp Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 15
DPT_Switch Channel A - Slave zero Output R-CT [1.1] 1 Bit position status DPT_Switch Channel A - Drive is moving Output R-CT 1 Bit 1.xxx Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 16
Channel A - Blocking 4 - Input RWC- [9.5] 2 Bytes Wind blocking DPT_Value_Wsp measurement value Channel A - Blocking 4 - Output R-CT [1.1] 1 Bit Wind blocking status DPT_Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 17
R-CT [1.1] 1 Bit DPT_Switch Channel A2 - Status Readable R-C- [1.1] 1 Bit DPT_Switch Channel A2 - Blocking Input RWC- [1.1] 1 Bit object DPT_Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
(Channels are divided into two switches A1|A2): • General specifications for the switch function (see Output channel with drive, page 46) • Connecting different communication objects (see Connection (switch functions), page 51) Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
0 ... 600 positions in 10 ms (only for manual input) for slat movement from closed 0 ... 600 position in 10 ms (only for manual input) Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 24
(retracting when shading, closing windows). Perform a reference movement no • yes Perform a reference movement for more than 1 ... 255; 10 movements before an auto positioning movement Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
(see graphic in chapter Connection options for zero position sensors in the general part). Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 26
(communication object). Use movement range limit Zero position sensor connected as • communication object • input channel Actuator is master • slave Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 27
• yes, as wind blocking • yes, as rain blocking Use block 4 • no • yes, with blocking object • yes, as wind blocking • yes, as rain blocking Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 28
(if "Expiration of a waiting period" was chosen) Switch to automatic for an object value 0 • 1 • 0 or 1 (if "Receipt of an object" was chosen) Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 29
Slat position in % (only if by using a block, 0...100 a specific shutter position is achieved) If blocking object has value =0 Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 30
For automatic operation after blocking follow automatic 16 bit input object: Type of input object 16 bit As of wind speed in m/s 2...30; 5 blocking Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 31
Behaviour after waiting period For manual operation before and after • no action blocking • move into last position For automatic operation after blocking follow automatic Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
= 1, short-term = 1 Use learning object for new position no • yes Transfer when programming • all parameters (when learning object is used) • changed parameters only Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
The time control is provided via a communication object. The input object "twilight control" is linked with the output object of a brightness sensor. A 1bit object (smaller Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 34
1 … 100; 20 Send current blocking status no • yes Shading is allowed if the measurement value is greater than or equal to the target value+difference Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 35
The threshold value is received via the communication object and can be changed additionally (e.g. button for "more sensitive" and "less sensitive"). Set the delay times Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 36
Azimuth from 0 … 360 Azimuth to 0 … 360 Elevation from 0 … 90 Elevation to 0 … 90 Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 37
Shutter position in % 0 … 100 Use teaching object for new shading no • yes position (only the curtain position will be saved, see info below) Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Ventilation is allowed if the measurement value is larger than the threshold value+hysteresis and blocked if the measurement value is smaller than or equal to the threshold value. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 39
Ventilation is allowed if the outdoor measurement value is smaller than the target value+difference-hysteresis and blocked if the outdoor measurement value is greater than or equal to the target value+difference. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 40
• not retained • after voltage returns • after voltage returns and programming Start threshold value in 0.1°C 100 … 500; 300 valid until 1st communication Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 41
If the ventilation is controlled by temperature and humidity via a 16bit input object, then you can either set an opening position or open the windows incrementally. In the Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Window position in % Slat position in % 0...100; 70 (only for shutters) 6.2.1.7.Button inputs (drives) Depending on the model, there are no inputs, two or four inputs. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 43
• send 0 • send 1 • do not send telegram Command when releasing the button • send 0 • send 1 • do not send telegram Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 44
If the input to the drive control is used via the bus, select the bus function "shutter", "awning", "blinds" or "window" and specify the button function and control mode. Function Shutter / blinds / awning / window Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 45
If the input is to be used as an 8bit encoder, select the "8 bit encoder" bus function and specify which value will be sent. Function 8 bit encoder Value 0...255 Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 46
Scene No. 0...127 The input can be blocked using a blocking object. For active blocking there is no bus communication. Use blocking object No • Yes Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 47
Control modi for drive control, page 47. The input can be blocked using a blocking object. No operation is possible for an active block. Use blocking object No • Yes Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Time between short and long 1...50; 10 in 0.1 seconds Repeat the step command every 0.1 s • every 2 sec; every 0.5 sec for a long button press Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 49
The drive moves as soon as the button is actuated and stops as soon as the button is released. Control mode Dead man's switch Behavior during button operation: Push button = Up or Down command Release button = Stop command Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
IN 1 IN 1 Master command Master Slave Master zero position status Drive 1 Drive 2 Slave zero position status at channel A at channel B Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 51
Zero position reached IN 1 Master command Master Slave Master zero position status Drive 1 Drive 2 Slave zero position status at channel A at channel B Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
AND or OR. E.g. a light can only be switched on if the button input is active AND twilight is active. Connection type AND • OR Value of the connection object 0 • 1 after bus voltage returns Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Time basis 0.1 s • 1 s • 1 min • 1 h Time factor 4...255; 10 Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
If a button with switch function is assigned to the input, select the button function "Switch" and specify what happens when pressing/releasing the button and when to send. Button function Switch Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
6.3.1. Temperature threshold value 1, 2, 3, 4 Threshold value: ------------------------------ Set the threshold values directly in the application program using parameters, or define them via the bus using a communications object. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 57
Set the behaviour of the switching output when a threshold value is exceeded/ undercut. The output switching delay can be set using objects or directly as a parameter. Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 58
Switching output sends on change to 0 • Do not send message • If switching output = 0 send 0 Switching output sends on change and Send switching output status periodically Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
Page 59
If switching output = 1 send 1 Switching output sends on change to 1 and periodically If switching output = 0 send 0 Switching output sends on change to 0 and periodically Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.