elsner elektronik KNX K8 Installation And Adjustment page 18

Actuator for heating and cooling
Table of Contents

Advertisement

If the comfort set point value is used as a basis:
If the comfort set point value is used as a basis, the deviation from this value is set.
Reduce nominal heating value (in 0.1°C)
for heating
Increase nominal cooling value\r\n (in
0.1°C)
for cooling
Eco set point
Eco mode is usually used for night mode.
If set point values are entered separately:
A starting set point value is defined as well as a temperature range in which the
nominal value may be modified.
Initial heating/cooling set point (in 0.1 °C)
valid till 1st communication
Min. object value heating/cooling (in 0.1
°C)
Max. object value heating/cooling (in 0.1
°C)
If the comfort set point value is used as a basis:
If the comfort set point value is used as a basis, the deviation from this value is set.
Reduce nominal heating value (in 0.1°C)
for heating
Increase nominal cooling value\r\n (in
0.1°C)
for cooling
Set point values for frost/heat protection (building protection)
The building protection mode is used during longer absences. Set points for frost
protection (heating) and heat protection (cooling) are determined which may not be
modified from outside (no access via operating devices etc.). The building protection
mode may be activated with delay, which allows you to leave the building before the
controls switch to frost/heat protection mode.
Nominal value frost protection\r\n (in 0,1°C)
Nominal value heat protection (in 0,1°C)
Activation delay
General variables
This setting appears for the control types "Heating and Cooling" only. This is where
you can decide whether to use a common variable for heating and cooling. If the 2nd
level has a common variable, this is also where you determine the control mode of the
2nd level.
KNX K8 actuator • Status: 18.11.13 • Technical Changes and Errors excepted.
17
0...200; 30
0...200; 30
-300...800; 210
-300...800; 160
-300...800; 280
0...200; 50
0...200; 60
-300...800; 70
-300...800; 350
no • 5 s • ... • 5 min • ... • 2 h
Parameter setting