6.2.1. Channel settings – drives
If a drive is connected to the output channel, set first the general specifications for the
drive.
Driving direction:
Up/down, on/off or open/close can be exchanged.
Exchange UP/DOWN (shutter, blinds)
Exchange ON/OFF (awning)
Exchange OPEN/CLOSE (window)
Runtime:
The runtime between the end positions is the basis for moving into intermediate
positions (e.g. for movement range limits and scenes). You can enter the runtime
numerically (in seconds) or have the runtime determined automatically. The actuator
specifies the end positions with help from the greater current on the drive output. For
this, regular reference movements (see below) should be set.
Use an automatic runtime measurement
Use an automatic runtime measurement
Runtime DOWN in sec (shutter, blinds)
Runtime OFF in sec (awning)
Runtime UP in sec (window)
Runtime OPEN in sec (shutter, blinds)
Runtime ON in sec (awning)
Runtime CLOSE in sec (window)
If a dead time is observed while starting the curtain, then this can be entered manually
at this point or calculated automatically. Obey the manufacturer's instructions for the
curtain.
Use dead times
during the position travel from closed
position in 10 ms (only for manual input)
for position movement from all other
positions in 10 ms (only for manual input)
for slat movement from closed
position in 10 ms (only for manual input)
Actuator KNX S1R-BA4-UP 24 V • Version: 27.05.2020 • Technical changes and errors excepted.
21
no • yes
no • yes
no
1 ... 320; 60
1 ... 320; 65
• no
• yes, enter by hand
• yes, calculate automatically
0 ... 600
0 ... 600
0 ... 600