Reference Manual
5.5

Application Alarms

Table 5-3 - 56WM Application Alarms (See section 2.5.9 Application Alarms of this manual for
more information)
Device Status
Voltage L1
Low
Voltage L2
Low
Voltage L3
Low
Voltage L1-L2
Imbalance
Voltage L2-L3
Imbalance
Voltage L1-L3
Imbalance
Description
Voltage L1-to-Neutral is less than
defined tolerance
Voltage L2-to-Neutral is less than
defined tolerance
Voltage L3-to-Neutral is less than
defined tolerance
Voltage L1-L2 is less than the
defined tolerance for imbalance
with the other line voltages
Voltage L2-L3 is less than the
defined tolerance for imbalance
with the other line voltages
Voltage L1-L3 is less than the
defined tolerance for imbalance
with the other line voltages
Recommended Action
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
voltage connector on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. Reset the device
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
voltage connector on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. Reset the device
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
voltage connector on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. Reset the device
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
voltage connector on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. Reset the device
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
voltage connector on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. Reset the device
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
voltage connector on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. Reset the device
December 2017