Specifications

Service Type
Power Input
Fuse
Voltage Channels
Current Channel
Overvoltage Category
Line Frequency
Waveform Sampling
Accuracy
Power Meter Safety
Current Transformer Safety
EMC
Temperature
Relative Humidity
Enclosure
Ingress Protection
Update Rate
HART Variables
Specifications
Single Phase, 3 Phase 4 Wire (WYE), 3 Phase 3 Wire (DELTA)
L1-L2 Phase 80-600VAC or USB 5VDC, 100mA
0.5A Time-Delay CC Class, 200kAIC, 600VAC
80-346VAC Line-to-Neutral, 600VAC Phase-to-Phase
0.520VAC max, 0.333VAC CTs, 0-4000A
CAT III, 600VAC
50/60 Hz
200 samples/60Hz waveform, 240 samples/50Hz waveform
0.2%, ANSI C12.20-2010 Class 0.2, True RMS Measurement
UL 61010-1, UL 61010-2-30, CSA C22.2 No. 61010-1
For use with UL 2808 listed CTs only
IEC 61326-1:2012 Class B
-20°C to 55°C
Up to 90% RH, Non-Condensing
ABS Plastic, 94-V0 flammability rating
IP20
1 minute (default), 1 second to 60 minutes
39 Device Variables (Default)
December 2017