Emerson 56WM WirelessHART SensEnable Reference Manual page 36

Power meter
Table of Contents

Advertisement

Reference Manual
Current L1
Imbalance
Current L2
Imbalance
Current L3
Imbalance
Line Frequency
Tolerance
Power Factor
L1 Low
Power Factor
L2 Low
Current L1 is less than the defined
tolerance for imbalance with the
other line currents
Current L2 is less than the defined
tolerance for imbalance with the
other line currents
Current L3 is less than the defined
tolerance for imbalance with the
other line currents
Line frequency is outside the
defined tolerance of the expected
line frequency
Power Factor L1 is less than the
defined minimum
Power Factor L2 is less than the
defined minimum
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
current connector on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. Reset the device
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
current connector on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. Reset the device
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
current connector on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. Reset the device
1. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
voltage connector on the device
2. Check voltage source for potential failures
3. Increase the defined tolerance
4. Reset the device
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
current and voltage connectors on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. If the asset is a motor, verify that the motor is
sized appropriately
6. Reset the device
1. Check load being monitored for potential failure
2. WARNING! Turn off power to the device and
verify that all wires are securely connected to the
current and voltage connectors on the device
3. Check voltage source for potential failures
4. Increase the defined tolerance
5. If the asset is a motor, verify that the motor is
sized appropriately
6. Reset the device
December 2017
34

Advertisement

Table of Contents
loading

Table of Contents