Table 2-5 - Minimum Data Scalar Settings - Emerson 56WM WirelessHART SensEnable Reference Manual

Power meter
Table of Contents

Advertisement

Reference Manual
The table below are the minimum recommended scalar settings based on current transformer size.

Table 2-5 - Minimum Data Scalar Settings

Current Transformer
Size or Max Amperage
To determine the appropriate data scalar for an application, use the following formula:
Measured or Calculated Values / Data Scalar Value ≤ 65,535 (Register Value)
If the data scalar is too low, the data may be inaccurate. If the data scalar is too high, the significant
digits after the decimal are removed. Below is an example of how to calculate the appropriate data
scalar.
Example 1:
Voltage = 480V
Amperage = 100A
Total System Power = (480V) * (100A) * 3 = 144kW
Select Data Scalar = 2, therefore data scalar value is 0.01
Register Value = 144kW / 0.01 = 14,400
Check 14,400 ≤ 65,535: Yes this data scalar is correct.
Example 2:
Voltage = 480V
Amperage = 1000A
Total System Power = (480V) * (1000A) * 3 = 1,440kW
Select Data Scalar = 1, therefore data scalar value is 0.001
Register Value = 1,440kW / 0.001 = 1,440,000
Check 1,440,000 ≤ 65,535: No this data scalar is incorrect.
Change the data scalar value and check result again.
240 Volts
50
Data Scalar = 1
100
Data Scalar = 2
200
Data Scalar = 2
400
Data Scalar = 2
600
Data Scalar = 2
1000
Data Scalar = 3
3000
Data Scalar = 3
3-Phase System Voltage
480 Volts
Data Scalar = 2
Data Scalar = 2
Data Scalar = 2
Data Scalar = 2
Data Scalar = 3
Data Scalar = 3
Data Scalar = 3
December 2017
16

Advertisement

Table of Contents
loading

Table of Contents