Specifications; Table 5: Specifications - Bosch D9412G Operations & Installation Manual

Table of Contents

Advertisement

D9412G/D7412G | Operation & Installation Guide |
2.2

Specifications

Table 5: Specifications

Voltage Input*
Primary:
(Power Supply)
Secondary:
Current
Panel : 500 mA alarm, 200 mA idle
Requirements
See Section 4.1 Current Rating Chart for Standby Battery Calculations in the D9412G/D7412G Approved
Applications Compliance Guide for the current draw requirements of other system components.
Power Outputs*
All external connections are inherently power-limited except battery terminals.
Continuous
Power Outputs
Alarm Power
Output
Switched Aux
Power
Fire and
Fire/Burglary
Systems
Minimum
10.2 VDC
Operating
Voltage
SDI Bus A (+):
SDI Bus
SDI Bus B (-):
Telephone
Connection:
Two TelCo
Connections
Lines:
Battery
Discharge
Discharge/
Cycle
Recharge
Schedule
Recharge
Cycle
Environmental
Temperature:
Relative
Humidity:
Arming
D720 Command Center, D1255 Command Center, D1256 Fire Command Center; D1257 Fire Alarm
Annunciator; D1260 Alpha V Command Center; Keyswitch
Stations
Point
On-board
Points 1 to 8
Thresholds
Compatible
D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack Resistant Enclosure
Enclosures
*The black and white circles with numbers indicate the specific panel terminal.
Bosch Security Systems | 10/03 | 43488E
2.0 Overview
16.5 VAC 40 VA class 2 plug-in transformer (D1640)
Sealed lead-acid rechargeable battery (12 VDC, 7 Ah or 12 VDC, 17.2 or
18 Ah). The panel supports a maximum of two 12 VDC, 7 Ah batteries
using the D122 Dual Battery Harness or two D1218 (12 VDC, 17.2 or 18
Ah) batteries using a D122.
1.4 A maximum at 10.2 VDC to 13.9 VDC (continuous supply) total for all
devices and outputs supplied at Terminals 3, 24, and 32 and at the
Accessory and Programming Connectors.
2.0 A maximum at 10.2 VDC to 13.9 VDC output. Output may be steady or
one of three pulsed patterns depending on programming. See Relays in the
D9412G/D7412G Program Entry Guide.
1.4 A maximum at 10.2 VDC to 13.9 VDC output. Continuous output is
interrupted by Sensor Reset or alarm verification depending on
programming. See Relays in the D9412G/D7412G Program Entry Guide.
To comply with UL 985 and 864 listing standards for fire alarm systems (effective March 1,
1989), the total combined continuous and alarm current draw for the system during alarm
conditions must be limited to 1.4 A (1400 mA) provided by the primary power supply (rectified
AC). If current draw for the system exceeds 1.4 A, remove connected devices until the current
draw falls below 1.4 A. Then, connect the removed devices to a D8132 Battery Charger
Module or to an external power supply (see Figure 26).
9 VDC 4572 m (15000 ft.) maximum
9 VDC 4572 m (15000 ft.) maximum
RJ31X or RJ38X jack can be interfaced with the panels.
Bosch Security Systems D928 Dual Phone Line Module required for two phone line service.
Supervision supplied by the panel.
13.9 VDC
Charging float level.
13.8 VDC
Charging status LED on.
12.1 VDC
Low Battery and AC Fail Reports if programmed. Low Battery LED on.
10.2 VDC
Battery load shed (processing functions continue if AC is present).
AC ON
Load shed relay resets, battery charging begins, Battery Trouble and AC
Restoral Reports sent.
13.7 VDC
Battery Restoral Report sent, Low Battery LED off.
13.9 VDC
Charging status LED off, battery float charged.
0°C to +50°C (+32°F to +122°F)
5% to 85% at +30°C (+86°F) non-condensing
Open
Greater than 3.7 VDC, but less than 5.0 VDC.
Normal
Greater than 2.0 VDC, but less than 3.0 VDC.
Short
Greater than 0.0 VDC, but less than 1.3 VDC.
EN | 12