Immediately perform an inspection after such faults.
Correct the cause of the fault as described in the respective remedial measures section. Repair
any damage to the machine.
8.9.2

Electrical faults

Note
If you are operating the motor with a converter, the operating instructions of the converter must
also be observed if electrical faults occur.
Table 8-1
Electrical faults
↓ Motor fails to start
↓ Motor accelerates sluggishly
↓ Rumbling noise during startup
↓ Rumbling noise during operation
↓ High temperature rise during no-load operation
↓ High temperature rise with load
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
SIMOTICS HV C 1NB1402-2AA84-4CA0-Z
Operating Instructions 06/2018
↓ High temperature rise of individual winding sections
Possible causes of faults
Overload
Interrupted phase in the supply cable
Interrupted phase in the feeder cable af‐
ter switching on
Mains voltage too low, frequency too high Check the power supply conditions.
Mains voltage too high, frequency too low Check the power supply conditions.
X
Stator winding incorrectly connected
X
Winding short circuit or phase short cir‐
cuit in stator winding
Incorrect direction of rotation
Remedial measures
Reduce the load.
Check the switches and cables.
Check the switches and cables.
Check the winding connection in the terminal box.
Determine the winding resistances and insulation
resistances. Carry out repair work after consulta‐
tion with the manufacturer.
Check the connection.
Operation
8.9 Faults
81