Honeywell SLG 700 User Manual page 57

Smartline level transmitter guided wave radar
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Probe Length
Step
Thread the nut onto the central conductor of the process connector. Refer to
Figure 3-6
between the locknut and the first rod segment. Torque the nut against the rod
segment and lock washer to secure the connection.
1
Note: Tighten rod connection point to the following torque:
SLG726 15Nm (11ft-lbs)
Slip the coaxial outer tube over the rod and tighten to the process connector.
Note: Tighten connection point to the following torque:
2
SLG726 30Nm (22ft-lbs)
It is recommended that a process compatible thread locking compound (i.e.
Loctite 242) be used on the outer conductor threaded joints.
Install end spacer between central conductor and outer tube in the
3
counterbore. Secure end spacer using the retaining ring.
Probe Length
Step
Thread the nut onto the central conductor of the process connector. Refer to
Figure 3-9 for nut position on flanged process connectors. Place a lock washer
between the locknut and the first rod segment. Torque the nut against the rod
1
segment and lock washer to secure the connection.
Note: Tighten rod connection point to the following torque:
SLG726 15Nm (11ft-lbs)
Slip the "starter" coaxial outer tube over the rod and secure to the process
connection using the M40x1 thread.
Note: Tighten connection point to the following torque:
2
SLG726 30Nm (22ft-lbs)
It is recommended that a process compatible thread locking compound (i.e.
Loctite 242) be used on the outer conductor threaded joints.
Prior to securing the next rod segment, place a "star shaped" spacer over the
3
rod segment end. The wrench flats on the rod end will index the spacer.
Depending on the probe length there could be 0 to 2 more rod segments and 1
rod "end" segment to assemble. Connect the subsequent rod segment to first,
using a stud and lock washer.
4
Note: Tighten rod connection point to the following torque:
SLG726 15Nm (11ft-lbs)
Slip a coaxial coupler over the last rod segment and spacer and tighten onto
the previous outer tube segment.
Note: Tighten connection point to the following torque:
5
SLG726 30Nm (22ft-lbs)
It is recommended that a process compatible thread locking compound (i.e.
Loctite 242) be used on the outer conductor threaded joints.
Revision 7
≤ 2.0m
for nut position on flanged process connectors. Place a lock washer
> 2.0m
SLG 700 SmartLine Level Transmitter User's Manual
Action
Action
Page 45

Advertisement

Table of Contents
loading

Table of Contents