Table 6-1: Slg 700 Standard Diagnostics Messages - Honeywell SLG 700 User Manual

Smartline level transmitter guided wave radar
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Critical Diagnostics
(Failure Conditions)
Active Diags
Sensor Module
Comm Module
Sensor Comm
Detail Diag
Sensor Int RAM
Sensor Ext RAM
Sensor Flash CRC
(Cyclic Redundancy Check)
Sensor Pwr Vosc
Sensor Pwr2.5V
Sensor Pwr 3.3V
Sensor Pwr Accum
Sensor Execution
Sensor Oscillator
Factory Mode
Revision 7

Table 6-1: SLG 700 Standard Diagnostics Messages

Description
Read-only field.
Displays the number of status flags in
the given category which are currently
in the Active or Alarm/Warning state.
Displays a status for the sensor.
Displays a status for the
communications module.
Displays a status for the sensor
communications.
This is a read-write parameter which
can be changed if you know the
Display Password (when enabled).
Displays a status of the internal RAM
on the sensor.
Displays a status of the external RAM
on the sensor.
Runs a background check on bits in the
database.
Error messages communicate
differences in encountered bits in the
database.
Failure encountered in sensing sector.
Failure encountered in sensing sector.
Failure encountered in sensing sector.
Displays a status of the power
accumulator.
Displays a status of sensor
performance.
Failure encountered in sensing sector.
Indicates the mode in which the
transmitter is currently running.
Factory mode allows users to run
HART commands.
SLG 700 SmartLine Level Transmitter User's Manual
Resolution
N/A
N/A
N/A
N/A
N/A
Electronics fault.
Repower the unit to clear the
fault. If error reoccurs,
replace the sensor
electronics.
Electronics fault.
Repower the unit to clear the
fault. If error reoccurs,
replace the sensor
electronics.
Execute HART commands to
exit factory mode.
Page 133