Table 4-8 Typical cable sizes for size 2 drives
Model
MP350A4(R) MP350A5(R) MP350A6(R)
MP420A4(R)
MP470A5(R) MP470A6(R)
MP550A4(R)
MP700A4(R) MP700A5(R) MP700A6(R)
MP825A4(R) MP825A5(R) MP825A6(R)
MP900A4(R)
MP1200A4(R) MP1200A5(R) MP1200A6(R)
MP1850A4(R) MP1850A5(R) MP1850A6(R)
* Values are beyond the mechanical design of the drive. At this power level it may be
prudent to consider busbars.
Notes for IEC 60364:
1. IEC 60364-5-52 table A 52-12 F method column 5 = Single core cable in free air.
NOTE
2. IEC 60364-5-52 table A52-14 correction factor for ambient air temperature others
than 30°C.
3. IEC 60364-5-52 table A52-17 item 4 correction factor for groups of more than one
circuit or more than one multi-core cable placed on a single layer on a perforated
tray.
Notes for US National Electrical Code:
1. Table 310.17 allowable ampacities of single-insulated conducted rated 0 through
NOTE
2000V in free air, based on ambient air temperature of 30 °C (87 °F).
2. Derating factor of 0.88 is applied for 40 °C to the 75 °C cable column. Table 310.17
is based on 30 °C (86 °F) ambient air temperature.
3. NEC 2005 edition table 310.15(B)(2)(a) shows the adjustment factors for more
than three current-carrying conductors in a race way or cable, for 4-6 current-
carrying conductors 0.80 derating factor is applied.
Mentor MP Short Form Guide
Issue Number: 5
Maximum
Continuous
input
output
current
current
A
A
295
350
350
420
395
470
450
550
585
700
665
825
725
900
1050
1200
1450
1850
www.controltechniques.com
IEC 60364-5-52
Table A52-12
Column 5 derated
by 0.91 for 40°C
XLPE cables (IEC
60364-5-52 table
Electrical Code
A52-14) and 0.77 for
cables bunching
(IEC 60364-5-52
table A52-17 item 4)
90°C cables at 40°C
75°C cable at 40°C
ambient
Input
Output
Input
size
size
cables
mm²
mm²
Kcmil
120
150
150
185
185
240
300
2 x 185
2 x 300
2 x 150
2 x 150
2 x 500
2 x 185
2 x 240
2 x 600
2 x 185
2 x 240
3 x 350
2 x 300
3 x 240
3 x 600
4 x 240
4 x 300
US National
ambient
Output
cables
Kcmil
350
400
400
500
500
600
2 x 350
2 x 600
3 x 350
3 x 400
4 x 400
*
*
43