Emerson Mentor MP Short Manual page 39

Hide thumbs Also See for Mentor MP:
Table of Contents

Advertisement

Table 4-2 Minimum required line inductance for a typical application (50% ripple content)
Drive
rated
current
A
25
45
75
105
155
210
350
420
470
550
700
825
900
1200
1850
1. The above assumes the supply has 1.5% impedance.
NOTE
2. Assumes a minimum supply rating of 5 kA and a maximum rating of 60 kA.
4.4.1
Auxiliary AC supply and connections
Table 4-3 Terminal functions
Terminals
E1, E3
L11, L12
F+, F-
MA1, MA2 Refer to the Mentor MP User Guide
Table 4-4 Line to line supply
Maximum nominal supply
Tolerance
Minimum nominal supply
Tolerance
Each drive has an onboard field controller with the following current ratings.
Mentor MP Short Form Guide
Issue Number: 5
System voltage
400V
480V
μH
μH
220
260
220
260
220
260
220
260
160
190
120
140
71
85
59
71
45
54
36
43
28
33
21
25
18
23
Supply for control electronics and field controller.
Field on / off. When L11 and L12 are open the supply is
disconnected to the field regulator so there will be no field
current.
Field supply to the motor.
Specification
www.controltechniques.com
current rating
575V
690V
μH
μH
320
320
320
320
230
170
110
120
80
91
53
61
45
52
31
36
29
32
Function
Typical
Maximum
current rating
A
A
21
22
38
40
63
67
88
94
130
139
176
188
293
295
351
350
393
395
460
450
586
585
690
665
753
725
1004
1050
1570
1655
Value
480 V
+10 %
208 V
-10 %
39