Caution: Only cartridges with the following part numbers can be fitted to the
Certified Sensor:
2110B30x0, 31x0, 32x0, 33x0, 34x0, 35x0 series
2110B3700 - 2110B3999 range
Note: For remote CSA Certified Sensor installations combustible cartridges in the range of part
numbers 2110B3700 to 2110B3799 MUST NOT BE FITTED.
Carefully plug the cartridge into the Certified Sensor body ensuring that the cartridge tab
lines up with the recess in the sensor body and push the cartridge, without twisting, until it is
fully home.
If the cartridge will not push fully home, re-check that the locating tab is correctly aligned with
the recess in the sensor body. Position the tab so it is resting on the tab recess wall to the
right or left of the tab recess and then turn the cartridge until the tab drops into the recess.
Caution:
Do not force the cartridge as this may cause damage to the pins of the connecting
plugs. Twisting and pushing can bend the pins and make the cartridge inoperative.
Socket (2 off)
Locating
tab
recess
Sensor body
Note: If fitting an Oxygen cartridge ensure that the Oxygen Transducer Adaptor supplied with the
Oxygen cartridge is fitted to the Certified Sensor body. The adaptor is fitted to the sensor
body via a bayonet fitting.
(3)
Refit the cap to the Certified Sensor.
Reverse the removal procedure.
3. inSTAllATiOn
53mm
Sensor body
Cartridge fitted to sensor
body
Sensor cap
37
Apex
Plug
(2 off)
Locating
tab
Cartridge