Fitting The Certified Sensor - Honeywell Apex Technical Handbook

Gas detection system
Hide thumbs Also See for Apex:
Table of Contents

Advertisement

MAN0604_Issue 09_02-2013
2110M8030
(4)
Fit and connect the field wiring.
See the subsequent tables and diagram for wiring details. Use either:
Conduit - using one or both of the ¾ NPT conduit entries. Ensure that a conduit sealing fitting
is installed within 18" of the enclosure on all conduit runs.
Cable - using any suitable flameproof cable entry device certified as Equipment to Directive
94/9/EC (ATEX).
Notes:
1.
All unused cable/conduit entries must be sealed with a certified sealing plug (one plug is
supplied fitted).
2.
For a multi-sensor system using a network loop, both cable/conduit entries are used, one
bringing the loop connections in and the other taking them out of the box. Remove the fitted
certified sealing plug from the spare cable/conduit entry.

3.2.2 Fitting the Certified Sensor

(1)
Fit the Certified Sensor to the Certified Junction Box.
Pass the sensor connecting cable through the sensor mounting point and then screw the
sensor firmly into the sensor mounting point until it is fully home.
(2)
Connect the sensor wiring.
See the following diagram and table for wiring details.
3. inSTAllATiOn
Certified Junction
Box base
Certified Sensor
mounting point
Certified Sensor
34