Honeywell Apex Technical Handbook page 72

Gas detection system
Hide thumbs Also See for Apex:
Table of Contents

Advertisement

MAN0604_Issue 09_02-2013
2110M8030
Calibration Info
This option displays a screen that reports information about the calibration of the Transmitter Unit
and Certified Sensor. An example of a typical screen is as follows:
Calibration Info
Last Calib:
Next Calib:
Gas:
FSD:
1.200 ppm
Calib Interval:
Predicted Life:
Last Calib
Next Calib
Gas
FSD
Calib Interval
Predicted Life
Current Config
This option displays 2 screens sequentially that report the current Transmitter Unit and Certified
Sensor configuration settings, e.g. alarm settings, relay configurations, etc.
Initial Screen
An example of a typical initial screen is as follows:
Current Config
Gas:
FSD:
1.200 ppm
Alarm1:
0.150 ppm
Alarm2:
0.300 ppm
Inhibit:
Warning:
Overrange
21.0 mA
Gas
FSD
Alarm1
Alarm2
Inhibit
Warning
Overrange
4. OPERATION
163
4205
PH3
4368
8571
Displays the time in hours since the last calibration was carried out.
Displays the time in hours to the next calibration based on the
calibration interval (Calib Interval).
Displays the type of gas cartridge fitted to the Certified Sensor.
Displays the maximum range of measurement.
Displays the calibration interval in hours.
Displays the typical life of the cartridge in hours.
PH3
1.2 mA
3.0 mA
Reports the type of gas cartridge fitted to the Certified Sensor.
Displays the maximum range of gas measurement.
Reports the alarm value set for Alarm1.
Displays the alarm value set for Alarm2.
Reports the value at which the 4-20mA Inhibit alarm is set to activate.
Displays the value at which the 4-20mA Warning alarm is set to
activate.
Reports the value at which the 4-20mA Overrange alarm is set
to activate.
Display Menu
Display Menu
72