Honeywell Apex Technical Handbook page 35

Gas detection system
Hide thumbs Also See for Apex:
Table of Contents

Advertisement

MAN0604_Issue 09_02-2013
2110M8030
Terminal/Number
SK1
1
SK2
2
SK3
3
4
5
SK4
1
2
g
-
* Only connect cable screens to these terminals if they are isolated at the
remote end.
Note: Three sensor wiring terminal blocks are provided (SK1, SK2 SK3), any
two can be used.
SK2
1
2
3
4
5
Internal earth
(3)
Configure the Certified Junction Box if required.
3. inSTAllATiOn
Function
Colour
CAN_L
White
CAN_H
Green or Blue
+V
Red
0V
Black
Not used
-
Screen *
-
Screen *
-
Earth
Green/Yellow
J1
SK3
1 2 3 4 5
SK1
SK4