Lonworks Communications Board; Lonworks Network Variables - Honeywell Apex Technical Handbook

Gas detection system
Hide thumbs Also See for Apex:
Table of Contents

Advertisement

MAN0604_Issue 09_02-2013
2110M8030
APPENDIX A - SPECIFICATIONS
A.4 LONWORKS COMMUNICATIONS BOARD
When fitted to a Transmitter Unit the LonWorks communications board provides an interface
between the unit and an open LON standard network.
The board consists of a Neuron micro-processor and associated memory and logic interface
components. Isolation to the network and correct signal levels are provided by an FTT-10A
transceiver device.
A.4.1 LonWorks Network Variables
The LIFELINE II gas detector has fourteen Network variable outputs, two network variable inputs
and four network configuration inputs as shown in the following LonMark Object Diagram.
Some or all of these may be bound to a LonWorks network. Descriptions of each variable are given
in the subsequent sub-sections. For more information consult Honeywell Analytics.
LIFELINE II Gas Detector
(SNVT_obj_request)
nviRequest
Node Object
nviResetAlm
(SNVT_lev_disc)
Open-Loop Sensor Object
nciAlarmSetT
(SNVT_elapsed_tm)
nciHighLim1
(SNVT_ppm_f)
nciHighLim2
(SNVT_ppm_f)
nciMaxSendT
(SNVT_elapsed_tm)
Virtual Function Block
LonMark Object Diagram
(SNVT_lev_disc)
nvoFaultD
(SNVT_switch)
nvoFaultS
(SNVT_obj_status)
nvoStatus
(SNVT_lev_disc)
nvoAlm2
(SNVT_lev_disc)
nvoAlmL
(SNVT_ppm_f)
nvoAlmThresh1
(SNVT_ppm_f)
nvoAlmThresh2
(SNVT_elapsed_tm)
nvoCellLife
(SNVT_str_asc)
nvoCellType
(SNVT_ppm_f)
nvoConc
(SNVT_ppm_f)
nvoConcFS
nvoConcType
(SNVT_str_asc)
(SNVT_elapsed_tm)
nvoLastCal
(SNVT_elapsed_tm)
nvoNextCal