Device:
ERR.ACT=NONE - OUT.ERR=NONE.
9116
If the valid range of the A/D converter or the polynomal is exceeded
Input
VOLT
CURR
LIN.R
POTM
TEMP
Input
All
Input
CURR
POTM
LIN.R
TEMP
Pt100 to Pt1000 and Ni50 to Ni1000
14
Configuration of sensor error check
Sensor error check:
Configuration
Else:
Visualisation in the 4511/4501 of:
Input signal outside range
Outside range readout (IN.LO, IN.HI):
Range
0...1 V / 0.2...1 V
0...10 V / 2...10 V
0...20 mA / 4...20 mA
0...800 Ω
0...10 kΩ
0 - 100%
TC / RTD
Display readout below min. / above max. (-1999, 9999):
Range
All
Sensor error detection
Sensor error detection (SE.BR, SE.SH):
Range
Loop break (4...20 mA)
All, SE.BR on all 3-wire
All
For Lin. R_0%≥ app. 18 Ω
All
9116 - Product version 9116-003
Sensor error detection:
OFF
ON
Readout
IN.LO
< -25 mV
IN.HI
> 1.2 V
IN.LO
< -25 mV
IN.HI
> 12 V
IN.LO
< -1.05 mA
IN.HI
> 25.05 mA
IN.LO
< -10 Ω
IN.HI
> 900 Ω
IN.LO
<-10 Ω
IN.HI
> 11 kΩ
IN.LO
< -0.5 %
IN.HI
> 100.5 %
IN.LO
< temperature range -2°C
IN.HI
> temperature range +2°C
Readout
-1999
Display readout <-1999
9999
Display readout >9999
Readout
Condition
SE.BR
<= 3.6 mA; > = 21 mA
SE.BR
Sensor broken
SE.SH
Sensor shorted
Sensor broken or
SE.BR
wire resistance too high
SE.SH
Sensor shorted
Sensor broken or
SE.BR
wire resistance too high
SE.SH
Sensor shorted
Limit
Limit