Page 1
3 1 0 0 6 m m S e r i e s o f I s o l a t o r s a n d C o n v e r t e r s M o d e l s n o . 3 1 0 3 / 3 1 0 4 / 3 1 0 5 / 3 1 0 8 / 3 1 0 9 N o .
Page 2
PR electronics A/S tilbyder et bredt program af analoge og digitale signalbehandlingsmoduler til industriel automation. Programmet består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere, Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv barske miljøer med elektrisk støj, vibrationer og temperaturud- sving, og alle produkter opfylder de strengeste internationale stan- darder.
Page 3
6 mm SerIeS of ISolatorS and ConverterS 3103 / 3104 / 3105 / 3108 / 3109 ContentS Warning ..................Safety instructions ................UL installation ................cFMus installation in Division 2 or Zone 2 ........ IECEx, ATEX installation in Zone 2 ..........EC declaration of conformity ............
Page 4
Until the device is fixed, do not connect hazardous voltages to the device. repair of the device must be done by Pr electronics a/S only. WarnIng In applications where hazardous voltage is connected to in-/ outputs of the device, sufficient spacing or isolation from wires, terminals and enclosure to surroundings (incl.
Symbol IdentIfICatIon triangle with an exclamation mark: Read the manual before installation and commissioning of the device in order to avoid incidents that could lead to personal injury or mechanical damage. the Ce mark proves the compliance of the device with the essential requirements of the directives.
Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively, Pr electronics a/S www.prelectronics.com Mounting and connection of the device should comply with national legislation for mounting of electric materials, i.e. wire cross section, protective fuse, and location.
The power supply unit must comply with NEC Class 2, as described by the National Electrical Code (ANSI / NFPA 70). ® cfmus InStallatIon In dIvISIon 2 or Zone 2 Class I, Div. 2, Group A, B, C, D T4 or I, Zone 2, AEx nA IIC T4 or Ex nA IIC T4. In class I, Division 2 or Zone 2 installations, the subject equipment shall be mounted within a tool-secured enclosure which is capable of accepting one or more of Class I, Division 2 wiring methods specified in the National Electrical...
Page 8
To the extent the instructions in this manual are not strictly observed, the customer cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement. CONTENTS 3100V1 0 6 -I N...
ConformIty As manufacturer Pr electronics a/S lerbakken 10 dk-8410 rønde hereby declares that the following products: type: 3103, 3104, 3105, 3108 and 3109 are in conformity with the following directives and standards: The EMC Directive 2004/108/EC and later amendments...
130 units. units can be supplied. Protective fuse: 2.5 A. Protective fuse: 2.5 A. Protective fuse: PR 9410. Protective fuse: 0.4 A. With the power control unit Alternatively, the 24 V supply voltage can 9410 redundant supply is be distributed via a power rail that receives possible.
moUntIng and demoUntIng of SyStem 3000 Picture 1: Mounting on DIN rail / power rail. Click the device onto the rail Picture 2: Demounting from DIN rail / power rail . First, remember to demount the connectors with hazardous voltages. Detach the device from the rail by lifting the bottom lock.
InStallatIon of SyStem 3000 on 7.5 mm dIn raIl 3,5 mm To avoid short circuit between the power rail connectors on the 3000 devices and the screws holding the 7.5 mm DIN rail, the head of the screws shall be no more than 3.5 mm high.
Page 13
6 mm SerIeS of ISolatorS and ConverterS 3103 / 3104 / 3105 / 3108 / 3109 The product family 3103, 3104, 3105, 3108 & 3109 are slimline isolaters for 24 VDC fixed supply and can be used for different purposes. Highlights •...
Page 14
Product overview Pr type no. 3103 3104 3105 Pr product name Isolated repeater Isolated converter Isolated converter description Fixed loop Loop isolator / Loop isolator / isolator / repeater. converter for converter for standard DC standard DC signals. signals. DIP-switch setup.
Page 15
Pr type no. 3108 3109 Pr product name Isolated repeater / splitter Isolated converter / splitter description Fixed loop isolator / Loop isolator / repeater with dual output. converter for standard DC signals. DIP-switch setup. Dual output. Parameterisation None DIP-switch Input signal 0/2…10 V...
electrical specifications Specifications range ........-25°C to +70°C Specifications range, 3105 ......0 to +70°C Storage temperature ........-40°C to +85°C Supply voltage, DC ........16.8...31.2 VDC Max. consumption........≤ 1.2 W Max. consumption, 3103, -05 & -08 ... ≤ 0.8 W Isolation voltage, test / working ....
Page 17
Current output Signal range (span) ........0...23 mA Programmable signal ranges ...... 0...20 / 4...20 mA Load (max.), 3103, 3104 & 3105 ....23 mA / 600 Ω / 13.8 VDC Load (max.), 3108 & 3109 ......23 mA / 300 Ω / 6.9 VDC Load stability ..........
Page 18
ConneCtIonS Output Input ch. 1 Supply Output ch. 2 81 82 83 84 85 Input signals 3103 3104 3105 3108 3109 Current Voltage output signals 3103 3104 3105 3108 3109 Current 1 Voltage 1 Current 2 Voltage 2 Supply 3103 3104 3105 3108...
InStallatIon on PoWer raIl Module stop All devices can be installed on a power rail (PR part number 9400) supported, if necessary, by module stop for power rail (PR part number 9403). Power supply units can be mounted on the power rail according to customer requirements.
dIP-SWItCH ProgrammIng The devices 3104, 3105 and 3109 can be configured via DIP-switches. The DIP- switches are located on the side of the device and can be adjusted with a small screwdriver or other implement. Adjustment of DIP-switches. Default factory settings are: Input = 0…20 mA Output = 0…20 mA All DIP-switches in the OFF position...
Page 21
3105 Input setup output setup 0…20 mA NA OFF OFF OFF 0…20 mA OFF OFF OFF NA 4…20 mA NA OFF ON OFF 4…20 mA OFF ON OFF NA 0…10 V ON OFF OFF 0…10 V ON OFF OFF NA 2…10 V ON OFF 2…10 V...
led IndICatIon The device is equipped with a green power LED in the front to indicate the operation status, see the table below. output and Condition action required loop supply No supply / Connect supply / device error or De-energized replace device code-flash CRC error 1 Flash...
Page 23
displays Programmable displays with a wide selection of inputs and outputs for display of temperature, volume and weight, etc. Feature linearisation, scaling, and difference measurement functions for programming via PReset software. ex interfaces Interfaces for analogue and digital signals as well as HART signals between sensors / I/P ®...