PR 9116 Series Product Manual page 11

Universal converter
Hide thumbs Also See for 9116 Series:
Table of Contents

Advertisement

EMC - immunity influence. . . . . . . . . . . . . . . . . . . . . . . . . < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst . . . . . . . . . . . . . . . . . . . . < ±1% of span
Auxiliary supplies for 9116B1:
2-wire supply (terminal 54...52) . . . . . . . . . . . . . . . . . . . . . . . . . . . 28...16.5 VDC / 0...20 mA
Auxiliary supplies for 9116B2:
2-wire supply (terminal 54...52) . . . . . . . . . . . . . . . . . . . . . . . . . . . 21.4...16.5 VDC / 0...20 mA
RTD, linear resistance and potentiometer input:
Input type
Min. value
Pt100
-200°C
Ni100
Linear resist.
Potentiometer
Input for RTD types:
Pt10*, Pt20*, Pt50*, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000
Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.), RTD . . . . . . . . . . . . . . . . . . . . . . . 50 Ω
Sensor current; RTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nom. 0.2 mA
Effect of sensor cable resistance (3- / 4-wire), RTD . . . . . . . . . . . . . . . < 0.002 Ω / Ω
Sensor error detection, RTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable ON / OFF
Short circuit detection, RTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
* No short circuit detection for Pt10, Pt20 and Pt50
* No short circuit detection for Lin. R_0%≤ app. 18 Ω
TC input:
Type
Min. value
B
E
-100°C
J
-100°C
K
-180°C
L
-200°C
N
-180°C
R
S
T
-200°C
-200°C
U
W3
W5
LR
-200°C
Cold junction compensation (CJC):
via external sensor in connector 5910. . . . . . . . . . . . . . . . . . . . . . 20...28°C ≤ ±1°C
via internal CJC sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±(2.0°C + 0.4°C * ∆t)
∆t = internal temperature - ambient temperature
Sensor error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable ON or OFF
Sensor error current:
when detecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nom. 2 μA
else. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 μA
Current input:
Measurement range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...23 mA
Programmable measurement ranges . . . . . . . . . . . . . . . . . . . . . . . . 0...20 and 4...20 mA
Input resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nom. 20 Ω + PTC 50 Ω
Max. value
+850°C
-60°C
+250°C
0 Ω
10000 Ω
10 Ω
10000 Ω
Max. value
0°C
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+1300°C
-50°C
+1760°C
-50°C
+1760°C
+400°C
+600°C
0°C
+2300°C
0°C
+2300°C
+800°C
9116 - Product version 9116-003
Standard
IEC 60751
DIN 43760
-
-
Standard
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
-20...20°C and 28...70°C ≤ ±2°C
(only wire breakage)