TC input:
Min.
Type
value
B
+400°C
+1820°C
E
-100°C
+1000°C
J
-100°C
+1200°C
K
-180°C
+1372°C
L
-200°C
+900°C
N
-180°C
+1300°C
R
-50°C
+1760°C
S
-50°C
+1760°C
T
-200°C
+400°C
U
-200°C
+600°C
W3
0°C
+2300°C
W5
0°C
+2300°C
LR
-200°C
+800°C
Cold junction compensation (CJC)
via internally mounted sensor .................< ±1.0 °C
Sensor error detection, all TC types ........... Yes
Sensor error current:
when detecting ....................................... Nom. 2 µA
else .......................................................... 0 µA
Current input:
Measurement range .................................... -1...25 mA
Programmable measurement ranges .......... 0...20 and 4...20 mA
Input resistance ........................................... Nom. 20 Ω + PTC 50 Ω
Sensor error detection:
loop break 4...20 mA ............................... Yes
Voltage input:
Measurement range .................................... -20 mV...12 VDC
Programmable measurement ranges .......... 0...1 / 0.2...1 / 0...2.5 / 0.5...2.5 /
Input resistance ........................................... Nom. 10 MΩ
Output:
Frequency output:
Frequency range ......................................... 0...25000 Hz
Min. frequency (span) .................................. 0.001 Hz
Duty cycle (0...25000 Hz) ............................ 50% or
Programmable pulse time (f ≤ 500 Hz) ........ 1...1000 ms (max. 90% duty cycle)
36
36
Max.
value
Standard
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
0...5 / 1...5 / 0...10 and 2...10 VDC
PNP output:
I
max. ...................................................... 30 mA
out
V
.............................................................. 24 VDC ± 10%
out
C
.............................................................. 10 nF
out
typ. ....................................................... 20 Ω
R
out
Electromechanical counter .......................... 24 V / 135 mA / 20 ms / ≤ 10 Hz
NPN output:
I
max. ..................................................... 150 mA
sink
I
max. peak ............................................ 300 mA
sink
External voltage (terminal 23) max. ............. 55 VDC
C
.............................................................. 10 nF
out
typ. ....................................................... 10 Ω
R
out
TTL output:
I
max. ............................................ 15 mA
sink/source
I
peak ............................................ 100 mA
sink/source
V
.............................................................. 5 V ±5%
out
C
.............................................................. 10 nF
out
typ. ....................................................... 55 Ω
R
out
Sensor error detection:
Programmable ............................................. 0...26250 Hz
Observed authority requirements:
EMC 2004/108/EC ...................................... EN 61326-1
LVD 2006/95/EC .......................................... EN 61010-1
UL, Standard for Safety .............................. UL 508
of span = of the currently selected measurement range

Configuration of sensor error detection:

Module:
Configuration
OUT.ERR=NO
4222
Else:
Display readout on the 4501:
Display outside range:
Display readout below min. / above max. (-1999, 9999):
Input
Range
All
All
Standard:
Sensor error detection:
OFF
ON
Flashing
readout
Limit
-1999
Display readout <-1999
9999
Display readout >9999