LERBAKKEN 10, 8410 ROENDE DENMARK
Hazardous Classified Location
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC
or Class I, Zone 0/1 Group IIC, [Ex ia] IIC
0/4-20 mA
Current Source
Module 9116B 1/2
Terminal 51-52
Ui, Vmax
30 V
Ii, Imax
120 mA
Pi
900 mW
Ci
3 nF
Li
2 μH
Module 9116B 1/2
Terminals 51-52
Uo, Voc
16.6 V
IIC or A,B
Io, Isc
0.2 mA
IIB or C,E,F
Po
0.8 mW
IIA or D,G
Revision date:
2012-06-08
-20 ºC ≤Ta ≤ +60ºC
+
-
Group
Co
Lo
0.4 μF
100 mH
2.3 μF
100 mH 100mH/Ω
9.5 μF
100 mH 200mH/Ω
Version Revision
V6 R0
9116 - Product version 9116-003
Unclassified Location or
Hazardous Classified Location
Class I, Division 2 Group A,B,C,D T4
or Class I, Zone 2, Group IIC T4
4501
54
34
53
33
52
32
51
31
44
14
43
13
42
12
41
11
9116
Power Rail
4501
54
34
53
33
52
32
51
31
44
14
43
13
42
12
41
11
9116
Power Rail
Lo/Ro
25mH/Ω
Prepared by:
PB
9116QF01
Status relay, terminal (33,34)
Unclassified location installation:
Voltage max:
125 VAC / 110 VDC
Power max:
62.5 VA / 32 W
Current max:
0.5 A AC / 0.3 ADC
Zone 2 installation:
Voltage max:
32 VAC/ 32 VDC
Power max:
16 VA / 32 W
Current max:
0.5 A AC / 1 A DC
Relay output, terminal (13,14)
Unclassified location installation:
Voltage max:
250 VAC / 30 VDC
Power max:
500 VA / 60 W
Current max:
2 A AC / 2 ADC
Zone 2 installation
Voltage max:
32 VAC / 30 VDC
Power max:
64 VA / 60 W
Current max:
2 A AC / 2 ADC
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
253 V max. 400 Hz
m:
Page:
4/4
43