Flowserve D30 Installation, Operation & Maintenance Manual page 28

Compact digital positioner
Hide thumbs Also See for D30:
Table of Contents

Advertisement

TRVL range
Setting end positions
0%=0.0%
Select Out of Service.
Set percentage value for
desired end position
(e.g. 3%).
Set 0%
Select In Service.
Connect calibrator.
Move forward to desired end
position (0%) and press OK.
100%=100.0% Select Out of Service.
Set percentage value for
desired end position
(e.g. 97%).
Set 100%
Select In Service.
Connect calibrator. Move
forward to desired end
position (100%)
and press OK.
Trvl ctrl
Behavior at set end position
Set low
Choose between Free
(positioner will control until a
mechanical top is reached),
Limit (stop at set end
position), and Cut off (Default
value. Go directly to a
mechanical stop at a
redefined setpoint).
Set high
Similar to Set low.
Values
Select position for Cut off and
Limit at the respective end
positions.
Passcode
Setting passcode for
access to the menu
Numbers between 0000 and 9999 can be used
as passcodes. 0 = no passcode required.
Appearance
Language
Select menu language.
Units
Select units.
Def. Display
Select value(s) to be
displayed during service.
The display reverts to this
value 10 minutes after any
change is made.
On display
D30 Digital Positioner
Start menu
Orient
Par mode
Devicedata
HW rew
SW rew
Capability
HART
Profibus PA
Status
Device ID Serial number
Address
Tag
Descriptor
Date
Failsafe
Foundation Fieldbus
Device ID
Nod address Address on the bus provided
TAG–PD_TAG Name provided by the
Descriptor
Date
Sim jumper Simulate jumper, FF
28
FCD PMENIM0030-01-A5 – 05/18
Start in Basic menu or
Full menu.
Orientation of text on display.
Display of control parameters
such as P, I, D or K, Ti, Td.
General parameters.
Menu with HART parameters.
Only amendable with HART
communicator. It is possible
to read from display.
Indicates present status
1-126
Allotted ID
ID description
SW release date
Value = preset pos
Time = Set time +10sec=
time before movement
Valve act = failsafe
(preset pos) or last value
(present pos)
Alarm out= On/Off
Serial number
by the DCS system
DCS system
D30 positioner
SW release date
simulation functionality
activated = ON