Ac Mains Connection - Danfoss VLT AutomationDrive FC 302 Operating Instructions Manual

90–315 kw d-frame
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Electrical Installation

4.7 AC Mains Connection

Size the wiring according to the input current of
the frequency converter. For maximum wire sizes,
see chapter 8.1 Electrical Data.
Comply with local and national electrical codes
for cable sizes.
Procedure
4
4
1.
Connect the 3-phase AC input power wiring to
terminals R, S, and T (see Illustration 4.22).
2.
Depending on the configuration of the
equipment, connect the input power to the
mains input terminals or the input disconnect.
3.
Ground the cable in accordance with the
grounding instructions provided in
chapter 4.3 Grounding.
4.
When supplied from an isolated mains source (IT
mains or floating delta) or TT/TN-S mains with a
grounded leg (grounded delta), ensure that
parameter 14-50 RFI Filter is set to [0] Off to avoid
damage to the intermediate circuit and to reduce
ground capacity currents.
30
VLT® AutomationDrive FC 302
1
1
Mains connection (R, S, T)
2
Motor connection (U, V, W)
Illustration 4.22 Connecting to AC Mains
Danfoss A/S © 06/2015 All rights reserved.
2
MG34U402

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents