Electrical Installation
Stop
Start
Line Power
Speed
Control
Illustration 4.2 Example of Proper Electrical Installation Using
Conduit
NOTICE
EMC INTERFERENCE
Use screened cables for motor and control wiring, and
separate cables for mains input, motor wiring and
control wiring. Failure to isolate power, motor and
control cables can result in unintended behaviour or
reduced performance. Minimum 200 mm (7.9 in)
clearance between mains input, motor and control cables
is required.