Safety

2 Safety

2.1 Safety Symbols

The following symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.

2.2 Qualified Personnel

Correct and reliable transport, storage, installation,
operation, and maintenance are required for the trouble-
free and safe operation of the frequency converter. Only
qualified personnel are allowed to install and operate this
equipment.
Qualified personnel are defined as trained staff, who are
authorised to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Additionally, the qualified personnel must be
familiar with the instructions and safety measures
described in these operating instructions.

2.3 Safety Precautions

WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to perform installation, start-up, and maintenance
by qualified personnel can result in death or serious
injury.
Only qualified personnel must perform instal-
lation, start-up, and maintenance.
MG34U402
Operating Instructions
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor may start at any
time. Unintended start during programming, service, or
repair work can result in death, serious injury, or
property damage. The motor can start via an external
switch, a serial bus command, an input reference signal
from the LCP, or after a cleared fault condition.
To prevent unintended motor start:
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. Failure to wait the specified
time after power has been removed before performing
service or repair work, could result in death or serious
injury.
1.
2.
3.
Voltage [V]
3x400
3x400
3x500
3x500
3x525
3x525
3x690
3x690
Table 2.1 Discharge Time
Danfoss A/S © 06/2015 All rights reserved.
Disconnect the frequency converter from the
mains.
Press [Off/Reset] on the LCP before
programming parameters.
Completely wire and assemble the frequency
converter, motor, and any driven equipment
before connecting the frequency converter to
AC mains, DC supply, or load sharing.
Stop the motor.
Disconnect AC mains, permanent magnet type
motors, and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.
Wait for the capacitors to discharge fully, before
performing any service or repair work. The
duration of waiting time is specified in Table 2.1.
Power range [kW]
Minimum waiting time
90–250
110–315
110–315
132–355
55–250
90–315
55–250
110–315
2
2
(minutes)
20
20
20
20
20
20
20
20
7