WARNING/ALARM 17, Control word timeout
There is no communication to the frequency converter.
The warning is only active when parameter 8-04 Control
Word Timeout Function is NOT set to [0] Off.
If parameter 8-04 Control Word Timeout Function is set to [5]
Stop and Trip, a warning appears, and the frequency
converter ramps down to a stop and shows an alarm.
Troubleshooting
Check the connections on the serial communi-
cation cable.
Increase parameter 8-03 Control Word Timeout
Time.
Check the operation of the communication
equipment.
Verify a proper installation based on EMC
requirements.
7
7
WARNING/ALARM 20, Temp. input error
The temperature sensor is not connected.
WARNING/ALARM 21, Parameter error
The parameter is out of range. The parameter number is
reported in the display.
Troubleshooting
Set the affected parameter to a valid value.
WARNING/ALARM 22, Hoist mechanical brake
The value of this warning/alarm shows the type of
warning/alarm.
0 = The torque reference was not reached before timeout
(parameter 2-27 Torque Ramp Up Time).
1 = Expected brake feedback not received before timeout
(parameter 2-23 Activate Brake Delay, parameter 2-25 Brake
Release Time).
WARNING 23, Internal fan fault
The fan warning function is an extra protective function
that checks if the fan is running/mounted. The fan warning
can be disabled in parameter 14-53 Fan Monitor ([0]
Disabled).
For frequency converters with DC fans, there is a feedback
sensor mounted in the fan. If the fan is commanded to run
and there is no feedback from the sensor, this alarm
appears. For frequency converters with AC fans, the
voltage to the fan is monitored.
Troubleshooting
Check for proper fan operation.
Cycle power to the frequency converter and
check that the fan operates briefly at start-up.
Check the sensors on the heat sink and control
card.
WARNING 24, External fan fault
The fan warning function is an extra protective function
that checks if the fan is running/mounted. The fan warning
can be disabled in parameter 14-53 Fan Monitor ([0]
Disabled).
52
VLT® AutomationDrive FC 302
For frequency converters with DC fans, there is a feedback
sensor mounted in the fan. If the fan is commanded to run
and there is no feedback from the sensor, this alarm
appears. For frequency converters with AC fans, the
voltage to the fan is monitored.
Troubleshooting
WARNING 25, Brake resistor short circuit
The brake resistor is monitored during operation. If a short
circuit occurs, the brake function is disabled and the
warning appears. The frequency converter is still
operational, but without the brake function.
Troubleshooting
WARNING/ALARM 26, Brake resistor power limit
The power transmitted to the brake resistor is calculated as
a mean value over the last 120 s of run time. The
calculation is based on the DC-link voltage and the brake
resistor value set in parameter 2-16 AC brake Max. Current.
The warning is active when the dissipated braking power
is higher than 90% of the brake resistor power. If option [2]
Trip is selected in parameter 2-13 Brake Power Monitoring,
the frequency converter trips when the dissipated braking
power reaches 100%.
WARNING/ALARM 27, Brake chopper fault
The brake transistor is monitored during operation, and if a
short circuit occurs, the brake function is disabled and a
warning is issued. The frequency converter is still
operational, but since the brake transistor has short-
circuited, substantial power is transmitted to the brake
resistor, even if it is inactive.
Troubleshooting
WARNING/ALARM 28, Brake check failed
The brake resistor is not connected or not working.
Check parameter 2-15 Brake Check.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the
motor is missing.
Troubleshooting
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and the
motor is missing.
Danfoss A/S © 06/2015 All rights reserved.
Check for proper fan operation.
Cycle power to the frequency converter and
check that the fan operates briefly at start-up.
Check the sensors on the heat sink and control
card.
Remove the power to the frequency converter
and replace the brake resistor (see
parameter 2-15 Brake Check).
Remove power to the frequency converter and
remove the brake resistor.
Remove the power from the frequency converter
and check motor phase U.
MG34U402