Danfoss VLT AutomationDrive FC 302 Operating Instructions Manual page 52

90–315 kw d-frame
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Maintenance, Diagnostics an...
WARNING/ALARM 2, Live zero error
This warning or alarm only appears if programmed in
parameter 6-01 Live Zero Timeout Function. The signal on 1
of the analog inputs is less than 50% of the minimum
value programmed for that input. Broken wiring or a faulty
device sending the signal can cause this condition.
Troubleshooting
Check the connections on all the analog mains
terminals.
-
-
-
7
7
Check that the frequency converter programming
and switch settings match the analog signal type.
Perform an input terminal signal test.
WARNING/ALARM 3, No motor
No motor is connected to the output of the frequency
converter.
WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains
voltage imbalance is too high. This message also appears
for a fault in the input rectifier on the frequency converter.
Options are programmed in parameter 14-12 Function at
Mains Imbalance.
Troubleshooting
Check the supply voltage and supply currents to
the frequency converter.
WARNING 5, DC link voltage high
The DC-link voltage (DC) is higher than the high-voltage
warning limit. The limit depends on the frequency
converter voltage rating. The unit is still active.
WARNING 6, DC link voltage low
The DC-link voltage (DC) is lower than the low-voltage
warning limit. The limit depends on the frequency
converter voltage rating. The unit is still active.
WARNING/ALARM 7, DC overvoltage
If the DC-link voltage exceeds the limit, the frequency
converter trips after a certain time.
Troubleshooting
Connect a brake resistor.
Extend the ramp time.
Change the ramp type.
Activate the functions in parameter 2-10 Brake
Function.
50
VLT® AutomationDrive FC 302
Control card terminals 53 and 54 for
signals, terminal 55 common.
®
VLT
General Purpose I/O MCB 101
terminals 11 and 12 for signals, terminal
10 common.
®
VLT
Analog I/O Option MCB 109
terminals 1, 3, and 5 for signals,
terminals 2, 4, and 6 common.
Danfoss A/S © 06/2015 All rights reserved.
Increase parameter 14-26 Trip Delay at Inverter
Fault.
If the alarm/warning occurs during a power sag,
use kinetic back-up (parameter 14-10 Mains
Failure).
WARNING/ALARM 8, DC under voltage
If the DC-link voltage drops below the undervoltage limit,
the frequency converter checks if a 24 V DC back-up
supply is connected. If no 24 V DC back-up supply is
connected, the frequency converter trips after a fixed time
delay. The time delay varies with unit size.
Troubleshooting
Check that the supply voltage matches the
frequency converter voltage.
Perform an input voltage test.
Perform a soft charge circuit test.
WARNING/ALARM 9, Inverter overload
The frequency converter has run with more than 100%
overload for too long and is about to cut out. The counter
for electronic thermal inverter protection issues a warning
at 98% and trips at 100% with an alarm. The frequency
converter cannot be reset until the counter is below 90%.
Troubleshooting
Compare the output current shown on the LCP
with the frequency converter rated current.
Compare the output current shown on the LCP
with the measured motor current.
Show the thermal frequency converter load on
the LCP and monitor the value. When running
above the frequency converter continuous
current rating, the counter increases. When
running below the frequency converter
continuous current rating, the counter decreases.
WARNING/ALARM 10, Motor overload temperature
According to the electronic thermal protection (ETR), the
motor is too hot. Select whether the frequency converter
issues a warning or an alarm when the counter reaches
100% in parameter 1-90 Motor Thermal Protection. The fault
occurs when the motor runs with more than 100%
overload for too long.
Troubleshooting
Check for motor overheating.
Check if the motor is mechanically overloaded.
Check that the motor current set in
parameter 1-24 Motor Current is correct.
Ensure that the motor data in parameters 1–20 to
1–25 are set correctly.
If an external fan is in use, check that it is
selected in parameter 1-91 Motor External Fan.
Running AMA in parameter 1-29 Automatic Motor