Extreme Networks BlackDiamond 10K Series Installation Manual page 22

Table of Contents

Advertisement

Site Preparation
Wiring Closet Considerations
You should consider the following recommendations for your wiring closet:
• Ensure that your system is easily accessible for installation and service. See "Rack Specifications and
Recommendations" on page 26 for specific recommendations.
• Use appropriate AC power for your switch, as described in Table 6.
Table 6: AC power requirements
Country
Requirements
North America
13 A service receptacle, NEMA 5-15 for 110/220 VAC power supplies.
United Kingdom
10 A service receptacle, BS 1363 for 110/220 VAC power supplies.
International
10 A service receptacle, CEE 7/7 for 110/220 VAC power supplies.
Australia
10 A service receptacle, AS 3112 for 110/220 VAC power supplies.
Japan
15 A service receptacle, JIS 8303 for 110/220 VAC power supplies.
• Use a vinyl floor covering in your wiring closet. (Concrete floors accumulate dust, and carpets can
cause static electricity.)
• Prevent unauthorized access to wiring closets by providing door locks. Install the equipment in a
secured, enclosed, and restricted-access area, ensuring that only qualified service personnel have
access to the equipment.
• Provide adequate overhead lighting for easy maintenance.
• Ensure that each wiring closet has a suitable ground. All distribution racks and equipment installed
in the closet should be grounded.
• Ensure that all system environmental requirements are met, such as ambient temperature and
humidity.
NOTE
Extreme Networks recommends that you consult an electrical contractor for commercial building and
wiring specifications.
Temperature. Extreme Networks equipment generates a significant amount of heat. It is essential that
you provide a temperature-controlled environment for both performance and safety.
Install the equipment only in a temperature- and humidity-controlled indoor area that is free of airborne
materials that can conduct electricity. Too much humidity can cause a fire. Too little humidity can
produce electrical shock and fire.
The following are some general thermal recommendations for your wiring closet:
• Ensure that the ventilation in the wiring closet is adequate to maintain a temperature below 104° F
(40° C).
• Install a reliable air conditioning and ventilation system.
• Keep the ventilation in the wiring closet running during nonbusiness hours; otherwise, the
equipment can overheat.
22
Extreme Networks BlackDiamond 10K-Series Switch Installation Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Blackdiamond 10808

Table of Contents