Technical Data
( valid from hardware revision 2.0 )
Number of outputs
Current measurement range
Measuring inaccuracy
Sampling rate
Output switching ratings
Ohmic load
Capacitive load
Voltage
Maximum inrush current
Maximum load
Incandescent lamps
Halogen lamps 230V
Halogen lamps, electronic transformer**
Fluorescent lamps, not compensated
Fluorescent lamps, parallel comp.
Max. number of electronic transformers
Output life expectancy (mechanical)
Permitted wire gauge
Screw terminal
KNX busconnection terminal
Power supply
Power consumption KNX bus typ.
Operation temperature range
Enclosure
Dimensions MDRC (Space Units)
*
total current carrying capacity neighbouring outputs max. 32A
** low voltage halogen lamps with electronic transformer
Examplary circuit diagram AMS/AMI-0816.01
MDT technologies GmbH
51766 Engelskirchen
Tel.: + 49 - 2263 - 880
Fax: + 49 - 2263 - 4588
Stand: 0113
MDT Switch Actuator AMS/AMI
AMS-0416.01
AMS-0816.01
AMS-1216.01
4
2000 samples/500ms
max. 140uF at 16A
0,5 - 4,0mm² solid core
0,5 - 2,5mm² finely stranded
0,8mm Ø, solid core
< 0,3W
4SU
Papiermühle 1
knx@mdt.de
www.mdt.de
8
12
10mA - 20A
2%
16A
230VAC
400A/150µs
200A/600µs
2700W
2500W
1000W
1800W
1000W
14
1.000.000
KNX bus
< 0,4W
< 0,4W
0 to + 45°C
IP 20
8SU
12SU
AMI-0416.01
AMI-0816.01
AMI-1216.01
4
8
10mA - 20A
2%
2000 samples/500ms
16/20A*
max. 200uF at 16A
230VAC
600A/150µs
300A/600µs
3680W
3680W
2500W
3680W
2500W
28
1.000.000
0,5 - 4,0mm² solid core
0,5 - 2,5mm² finely stranded
0,8mm Ø, solid core
KNX bus
< 0,3W
< 0,4W
0 to + 45°C
IP 20
4SU
8SU
DIN EN ISO 9001
TAW Cert
Zert.Nr.1905606
N
12
< 0,4W
12SU

Advertisement

Table of Contents
loading

Table of Contents